How to execute the ACAL using the FF Transducer Block
It is also possible to perform the same calibration functions in the FF transducer block by using a set of
specific parameters (see section 8.12.2 for further information on the ICoT transducer block).
The equivalent command of
ACAL
in the Transducer block is available in the parameter
“PSNR_COMMAND” by selecting the option “Arm” and then selecting the option “Start Auto Cal”.
The ICoT FF will execute the same internal procedures as the command ACAL available in the local display
menu.
Manual Calibration (MCAL)
This menu give access to the following five calibration functions via the pushbuttons:
1.
Lo
- Low (Zero) Calibration
2.
Hi
- High (Span) Calibration
3.
PID
- Proportional, Integral and Derivative Gain Adjustment (
PID Auto
and
PID Manual
)
4.
Snsr
- Sensor Calibration
5.
Trnd
- Transducer Calibration
If advanced settings are required to fine tune the positioner, proceed with Manual Calibration Menu
(MCAL).