5/12/2017
TECH-538/D.W.O. 23160
Page 14 of 189
ICoT 6400
•
FF specific
o
ITK version: 6.1.2
o
PHY compliance: FF-830 FS2.0
o
MANUFAC_ID: 0x574343
o
DEV_TYPE: 0x1100
o
DEV_REV: 0x04
o
DD_REV: 0x02
o
N
o
of Blocks: 1xRB, 1xTB, 1xAI, 1xAO and 1xPID
o
Block execution time:(AI:52ms, AO:55ms; PID:100ms)
o
Device class: BASIC
o
More at:
http://www.fieldcommgroup.org/
•
Electrical input:
o
Connector: J1 (pins 1 and 2)
o
Grounding: J1 pin 5 (cable shield not connected)
o
Operating voltage: 9 to 32 VDC (Max 35 VDC overvoltage protected)
o
Polarity insensitive
o
Maximum current consumption from the bus: 12.5 mA
•
Real Time Clock:
o
Adjusted using Diagnostic Transducer Block
o
Back-up: Supercapacitor
o
Back-up life: 7 days @ 20
o
C (68
o
F)
•
Optional potentiometer sensor input (POT version):
o
Connector: J5
o
Recommend Industrial ruggedized 1kOhm to 10kOhms
o
Maximum wire length: using shielded twisted cable 3M (10 feet)
•
Optional 4-20mA sensor input (TOG version):
o
Connector: J5
o
Any sensor with a 4-20mA output and update rate at least 10 Hz
o
Maximum wire length: using shielded twisted cable 15M (50 feet)
- limited by pneumatic tubing
6
The device was tested against the ICoT FF firmware revision 4.2. For newer revisions consult Westlock.
7
For reference only. Check the actual device or consult Westlock for more information.