and working position.
only
24
POS_ALERT_HI
User defined high position threshold
that when FINAL_VALUE is more
positive will trigger a position high
alert. The alert is generated via the
standard Field Diagnostic mechanism
as defined in References
(FOUNDATION™ Specification,
Function Block Application Process
Part 1 – FF-890, Rev FS 1.10) and
(FOUNDATION™ Specification,
Function Block Application Process
Part 2 – FF-891, Rev FS 1.10).
0
0
0
%
25
POS_ALERT_LO
User defined low position threshold
that when FINAL_VALUE is more
negative will trigger a position low
alert. The alert is generated via the
standard Field Diagnostic mechanism
as defined in References
(FOUNDATION™ Specification,
Function Block Application Process
Part 1 – FF-890, Rev FS 1.10) and
(FOUNDATION™ Specification,
Function Block Application Process
Part 2 – FF-891, Rev FS 1.10).
0
0
0
%
26
RATED_TRAVEL
Nominal travel of actuator/valve in
travel units.
This is a read/write informative
parameter.
0
0
0
TU
27
STOP_HI_POS
1- User defined high limit for valve
position that when reached will set a
stop hi position limit bit. The alert is
generated via the standard Field
Diagnostic mechanism as defined in
References (FOUNDATION™
Specification, Function Block
Application Process Part 1 – FF-890,
Rev FS 1.10) and (FOUNDATION™
Specification, Function Block
Application Process Part 2 – FF-891,
Rev FS 1.10).
2- It also limits the Set Point. This
0
0
0
%
29
In the FF standard dictionary revision lower than the revision 3.80, the user may see this parameter with a different label: “Signal Action”. This is
a defect in the dictionary fixed in the revision 3.80 but old host systems may still use an old revision and therefore show the wrong parameter name,
giving the impression that there are two parameters with the same name (SIGNAL_ACTION)