Exiting Calibration (ACAL or MCAL)
To exit calibration mode and return to normal operation use the
up
key as follows:
1.
If the positioner is at
Menu level
in the calibration, as determined by local display showing a
menu name only (
MCAL
, etc.), press the “Up” button once to exit
CAL
mode.
2.
If the positioner is at
function level
in the calibration, as determined by local display showing a
function and Menu name only (
MCAL Lo
, etc.), press “Up” button once to enter the Menu level
and once more to exit
CAL
mode.
3.
If the positioner is performing any calibration function (e.g.,
ACAL Trnd
), press and hold “Up” and
“Down” buttons simultaneously to abort the current operation and go to the normal operation
screen.
4.
When the calibration mode is exited the Menu and function names will no longer be shown by
the local display. The local display will show “OK”.
How to exit the calibration in the Transducer Block
It is also possible to exit the calibration modes and return to normal operation via Transducer block
parameter “PSNR_COMMAND” by selecting the option “Abort”.