How to execute the Automatic Calibration in the Transducer Block
It is also possible to perform the calibration in the FF transducer block by using a set of specific
parameters (see section 8.12.2 for further information on the ICoT transducer block).
The equivalent command of the automatic calibration in the Transducer block is available in the
parameter “PSNR_COMMAND” by selecting first the option “Arm”
and then the option “Start Auto
Cal”. In this way the ICoT FF will execute the same internal procedures as the “Auto Calibration”
method available in the ICoT EDD menu.
Exiting Calibration
To exit calibration mode and return to normal operation use the
up
key as follows:
•
If the positioner is at
Menu level
in the calibration, as determined by LCD displaying a Menu name only
(
MCAL
, etc.), press the
up
key once to exit
CAL
mode.
•
If the positioner is at
function level
in the calibration, as determined by LCD displaying a function and Menu
name only (
MCAL Lo
, etc.), press the
up
key once to enter the Menu level and once more to exit
CAL
mode.
•
If the positioner is performing any calibration function (e.g.,
ACAL Trnd
), press up and down key
simultaneously to abort the current operation and go to the normal operation screen.
•
When the calibration mode is exited the Menu and function names will no longer be displayed by the LCD.
The LCD will be displayed “OK”.
How to exit the calibration in the Transducer Block
It is also possible to exit the calibration and return to normal operation using the Transducer block parameter
“PSNR_COMMAND” by selecting the option “Abort”.
20
This can be used as a squawk function. While the PSNR_COMMANDS is set to “Arm”, The first 14 characters of
the device’s tag is shown in the last row of the LCD