Installation & Operating Instructions

Westlock Accutrak / Quantum 2800

With Optional MAGNUM Proximity Switches.

Specifications

Operating Pressure: 

45-120 PSIG

Operating Temperature: 

-20

C to +85

C

Operating Media: 

Non Lubricated Filtered Air to 20 Microns

Field Wiring

Complete the electrical wiring in accordance with local and National Electrical Codes. The ground wire should be secure under the green
screw. Check all screws for tightness. If the installation is in a hazardous area, all electrical leads must be sealed with an approved com-
pound, in accordance with local and National Electrical Codes unless the switches are hermetically sealed. (NEC 5051-5)

Always check the nameplate to make sure the approval ratings coincide with the application.

CAUTION: To prevent ignition of hazardous atmospheres, replace cover before 

connecting

the electrical circuits.

Keep cover tightly closed when in operation.

(Air Line) Designation

1/4

NPT air ports for inlet, outlet, and exhaust 

Description of Operation:

Solenoid De-energized -

air flows from Inlet Port 1 to Outlet Port 2 and

exhausts from Port 4 to Port 5. Solenoid Energized -

air flows from Inlet Port 1 to Outlet Port 4 and

exhausts from Port 2 to Port 3.

Description of Operation:

Solenoid De-energized -

air flows from Outlet Port 2 to Exhaust Port 3.

Solenoid Energized - air flows from Inlet Port 1 to

Outlet Port 2.

(3.5 Cv valve has 1/2

NPT air ports)

Spring Return Valve

Spring Return Valve

WESTLOCK CONTROLS UK Ltd.

22 CHAPMAN WAY, TUNBRIDGE WELLS, KENT, TN2 3EF, ENGLAND. TEL: 44 (0)1892 516277 FAX: 44 (0)1892 516279

(Air Line) Installation Considerations

Air  Mains  and  lines  should  be  large  enough  to  avoid  excessive  pressure  loss  under  conditions  of  maximum  flow.  Air  lines  should  be
installed with as few restrictions as possible if the cost of compressed air is to be kept to a minimum. Sharp turns in piping should be
avoided for more effecient air flow and economical air power. It is advisable to pitch the mains in the direction of air flow so that both grav-
ity and air flow will carry the water to traps or water legs located at frequent intervals.

To help in preventing condensed moisture from reaching the point of usage, down pipes should never be taken directly from the bottom
of air pipes or mains. Connection should be made at the top of the main and a long radius return bend used

.