Unit is shipped from factory with Temporal (Code 3) selected (jumper to right). Installer can select Non-Temporal (Continuous) audible signal by moving the factory 
installed jumper to the left one position.  The jumper will be placed only on the left pin, leaving the circuit open to select Continuous. Detach ‘Beauty Plugs’ from rear 
of grille before installing unit. 

 

Figure 4: 

Figure 5: 

 

3/8"

 

 

ROUTE WIRE 

THROUGH 

NOTCH AS 

SHOWN

 

MOUNTING PROCEDURES: 

 
Use this mounting procedure to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  This is especially 
important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 
 

1. 

Bend the 4 field wires 90

°

 as shown in Figure 4. 

2. 

Connect the 2 field wires to each screw terminal (in-out wiring) and dress the 2 wires through the slot as shown in Figure 5 (polarity must be observed). 

3. 

Gently push the 4 field wires into the backbox by hand and screw the unit to the backbox. 

 
MOUNTING OPTIONS: 
 

CAUTION

:  The following figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option.  If these 

limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. 
 
Although the limits shown for each mounting option comply with the National Electrical Code (NEC), Cooper Wheelock recommends use of the largest backbox option 
shown and the use of approved stranded field wires, whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from 
wiring. 

SINGLE-GANG X 3-1/2"
DEEP BACKBOX

FLUSH MOUNTING

A

4

4

4

4

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

B

4

4

4

4

AWG #18  AWG #16  AWG #14  AWG #12

MAXIMUM NUMBER OF CONDUCTORS

SINGLE-GANG X 1-3/4"
DEEP WIREMOLD
BACKBOX

SURFACE MOUNTING

 

MOUNTING NOTES: 

CAUTION

:  Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed 

multiconductor cable or 3/4" conduit fittings are used. 

1. 

Mounting hardware for each mounting option is supplied. 

2. 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring space for the signaling appliance. 

3. 

Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  This is 
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

4. 

Do not pass additional wires (used for other than the signaling appliance) through the backbox.  Such additional wires could result in insufficient wiring space 
for the signaling appliance. 

5. 

Place ‘Beauty Plugs’ over screw heads after installation using the mounting hardware supplied. 

6. 

All models are UL Listed for indoor use with a temperature range of +32

°

F to +120

°

F (0

°

C to +49

°

C) and maximum humidity of 93% RH, 

±

2%. 