P84234H 

Sheet 2 of 4 

 
 
 

Table 3:  Current Ratings (AMPS) for 24VDC and 12VDC Wall Models  

Maximum RMS Current with Hi dBA Setting 

       Voltage 

NS-241575W 

Voltage 

NS-121575W 

DC 16.0VDC-33.0VDC 

0.104  8.0VDC-17.5VDC 

0.220 

FWR 16.0VRMS-33.0VRMS 

0.174 

8.0VRMS-17.5VRMS 

0.325 

Maximum RMS Current with Low dBA Setting 

       Voltage 

NS-241575W 

Voltage 

NS-121575W 

DC 16.0VDC-33.0VDC 

0.096  8.0VDC-17.5VDC 

0.210 

FWR 16.0VRMS-33.0VRMS 

0.160 

8.0VRMS-17.5VRMS 

0.320 

 

When calculating the total current:  Use Table 3 to determine the highest value of “RMS Current” for an individual NS then multiply the value by the total number of 
NS Appliances.  Be sure to add the currents for any other appliances powered by the same source and to include any required safety factors. 

NOTE:  

The maximum number of strobes on a single notification appliance circuit shall not exceed 50. 

CAUTION:  

These notification appliances are UL Listed as “Regulated”.  They are intended to be used with FACPs whose notification circuits are UL Listed as 

“Regulated.”  These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the 
installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual. 

WARNING:  THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS USING 

FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE.  DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.   

WARNING:  CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE 

VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES.  THE MAXIMUM 
WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.   

 

WARNING:  MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE 

SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, APPLIANCE CIRCUITS, SM, DSM SYNC MODULES AND WHEELOCK POWER 
SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS 
TO WHICH THESE APPLIANCES ARE WIRED.  OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS 
OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

CAUTION:  

These horn/strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off. 

 

SOUND OUTPUT (SPL) SETTINGS:

 

 

WARNING:  THE NS APPLIANCES MUST BE FIELD SET TO THE DESIRED TONE AND dBA SOUND OUTPUT LEVEL BEFORE THEY ARE 

INSTALLED.  THIS IS DONE BY PROPERLY INSERTING JUMPER PLUGS IN ACCORDANCE WITH THESE INSTRUCTIONS.  INCORRECT 
SETTINGS WILL RESULT IN IMPROPER PERFORMANCE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR 
DEATH TO YOU AND/OR OTHERS.

 

Figure 1: Showing Location of Jumper Plug 

  JUMPER 

  PLUGS

  TOP

PLUG

NO PLUG

HI

LOW

CODE 3

HORN

 

Factory setting is on High dB and Code 3. 

NOTE:

  The NS-24MCW must be set for Code 3 horn when installed on a synchronized notification appliance circuit (NAC). 

 

Figure 2:  Jumper plug settings for 

High dB and Code 3. 

Figure 3:  Jumper plug settings for Low 

dB and Continuous Horn. 

Figure 4:  Jumper plug settings for 

High dB and Continuous Horn.

 

Figure 5:  Jumper plug settings for Low 

dB and Code 3.

 

 

SHOWN 

SET ON 

HI dB 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON 

 CODE 3

 

(Use needle nose pliers to pull and 

properly set the jumper plugs.)

 

 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON

 CONT' HORN *

SHOWN 

SET ON 

LOW dB

 No jumper plugs are needed for 

Continuous Horn and low dB settings.  

 

 CENTER PIN 

 IS NOT USED

 SHOWN

 SET ON

 CONT' HORN *

SHOWN 

SET ON 

HI dB 

 

 

 

 CENTER PIN 

 IS NOT USED

SHOWN 

SET ON 

LOW dB

 SHOWN 

 SET ON 

 CODE 3

 

 