background image

P83984 E 

Sheet 5 of 9

 

WIRING INFORMATION: 
 
 
 

Figure 6:  Audible signal and strobe operate independently. 

 

 TO NEXT APPLIANCE

 OR EOLR

 TO NEXT APPLIANCE

 OR END OF LINE

 RESISTOR (EOLR).

  STROBE

  AUDIBLE

 FROM FIRE ALARM

 CONTROL PANEL (FACP)

 PRECEDING APPLIANCE

 OR SYNC MODULE *

 FROM FACP OR

 PRECEDING APPLIANCE

+

-

-     +

-     +

-

+

-

+

-

+

 

 
 
 

Figure 7:  Audible signal and strobe operate in unison .  Red and black shunt wires are supplied.

 

 

+

-

+

-

-

+

BLACK SHUNT WIRE

RED SHUNT WIRE

 TO NEXT APPLIANCE

 OR EOLR

   STROBE

   AUDIBLE

 FROM FACP

 PRECEDING APPLIANCE

 OR SYNC MODULE

+

-

 

 
 

*  When the sync module is used, the audible tone will be Code 3 sound only.  Refer to Sync Module Installation Instruction sheets 
SM (P83123), DSM (P83177) or PS-12/24-8 (P83862) for additional information.  Audible will operate only with power applied to 
both strobe and audible.

 

 
 
 

 Figure 8. 

 

 

 

 

 

 
 
 

1)  The NS4-MCW Appliance has in-out wiring terminals that accepts two #12 to 18 American Wire Gauge 

(AWG) wires at each screw terminal.  Strip leads 3/8” inches for connection to screw terminals. 

2)  Break all in-out wire runs on supervised circuit supervision as shown in Figures 6 and 7.  The polarity 

shown in the wiring diagrams is for the operation of the appliances.  The polarity is reversed by the 
FACP during supervision. 

 
 
 

Summary of Contents for NS4-24MCW

Page 1: ...on of circuit wiring by a FACP NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING THE NS HORN STROBE IS A FIRE ALARM DEVICE DO NOT PAINT NOTE All Canadian Installations should be in accordance with the Canadian Standard for the Installation of Fire Alarm Systems CAN ULC S524 01 and Canadian Electrical Code Part 1 Final acceptance is...

Page 2: ...30 1 210 The time duration for the peak current is 1 millisecond NOTE Inrush current is less than rated peak current Table 3A UL ULC Horn Current Ratings AMPS UL Voltage ULC Voltage High dBA Low dBA 16 0VDC 20 0VDC 0 019 0 012 24 0VDC 24 0VDC 0 028 0 015 33 0VDC 31 0VDC 0 039 0 018 16 0VRMS 20 0VRMS 0 029 0 016 24 0VRMS 24 0VRMS 0 044 0 019 33 0VRMS 31 0VRMS 0 061 0 022 WARNING MAKE SURE THAT THE ...

Page 3: ... 8 4 7 5 9 18 8 22 27 5 31 90 3 8 8 7 5 15 18 8 38 27 5 48 Table 4A Vertical Plane UL 1971 Vertical 15cd 30cd 75cd 110cd Angle in deg UL Min Typ 15cd UL Min Typ 30cd UL Min Typ 75cd UL Min Typ 110cd 0 15 0 23 30 0 49 75 0 116 110 0 155 5 13 5 26 27 0 51 67 5 123 99 0 166 10 13 5 21 27 0 42 67 5 105 99 0 139 15 13 5 19 27 0 39 67 5 95 99 0 134 20 13 5 19 27 0 36 67 5 82 99 0 116 25 13 5 17 27 0 34 ...

Page 4: ...t specified by ANSI NFPA for standard emergency evacuation signaling The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose Figure 1 Showing Location of Jumper Plug and Candela Selector JUMPER PLUGS CANDELA SELECTOR TOP PLUG NO PLUG HI LOW CODE 3 HORN STB AUD WARNING TO PREVENT ELECTRIC SHOCK DO NOT REMOVE THIS COVER NO USER SERVICEABLE PARTS INSIDE 15 75 1...

Page 5: ...DULE When the sync module is used the audible tone will be Code 3 sound only Refer to Sync Module Installation Instruction sheets SM P83123 DSM P83177 or PS 12 24 8 P83862 for additional information Audible will operate only with power applied to both strobe and audible Figure 8 1 The NS4 MCW Appliance has in out wiring terminals that accepts two 12 to 18 American Wire Gauge AWG wires at each scre...

Page 6: ...tress on the product from wiring C A B D FLUSH MOUNTING STD SINGLE GANG BACKBOX 6 32 X 7 8 SCREWS NS MOUNTING PLATE NSMP NS BEAUTY PLATE SUPPLIED MAXIMUM NUMBER OF CONDUCTORS BACKBOX DEPTH AWG 18 AWG 16 AWG 14 AWG 12 2 1 2 8 4 4 4 3 1 8 8 8 8 8 MAXIMUM NUMBER OF CONDUCTORS AWG 18 AWG 16 AWG 14 AWG 12 8 8 8 8 NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS MOUNTING PLATE NSMP NS BEAUTY PLATE SUPPL...

Page 7: ... for each mounting option is supplied 7 Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product 8 When terminating field wires do not use more lead length than required Excess lead length could result in insufficient wiring space for the signaling appliance 9 Use care and proper techniques to position the field wires in the backbox so th...

Page 8: ...idelines or restrictions on wiring and or locating Notification Appliance Circuits NAC and notification appliances Some system communication circuits and or audio circuits for example may require special precautions to assure electrical noise immunity e g audio crosstalk NOTE This equipment has been tested and found to comply with the limits for a Class B digital appliance pursuant to Part 15 of t...

Page 9: ... SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUIR...

Reviews: