1.

 

This RSS model can be flush mounted to a standard single-gang backbox (Figure A), 4” or 100mm backbox (Figure B) or double-gang backbox (Figure C).  It can 
also be surface mounted to a 4” or 100mm backbox (Figure B), double-gang backbox (Figure C) or the SHBB (Figure D).  Mounting hardware for each mounting 
option is supplied. 

2.

 

Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product.  Do not pass additional wires (used for other 
than the signaling appliance) through the backbox.  Such additional wires could result in insufficient wiring space for the signaling appliance. 

3.

 

When terminating field wires, do not use more lead length than required.  Excess lead length could result in insufficient wiring space for the appliance. 

4.

 

Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product.  This is 
especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 

5.

 

This RSS model has an integrated Strobe Mounting Plate (SMP) which must be oriented correctly when it is mounted to the backbox.  Turn the SMP so that the 
arrow above the words “Horizontal Strobe” points to the top side. 

6.

 

Move the selector switch to the desired candela setting.  The setting is indicated by a pointer and can be seen on the bottom side of the lens.  See Figures 3 and 4 
below. 

7.

 

Mount the SMP first to the backbox.  Next slide the cover over the SMP until the 2 snaps of the cover engage with the SMP. 

8.

 

The cover can be removed from the strobe assembly once engaged.  See Figure 5. 

 

Figure 3: 

95

 CANDELA

 POINTER

BOTTOM VIEW

30

15

75

 

NOTE

:  The RSS Multi-Candela come pre-set at 15cd.

 

Figure 4:

 

CANDELA

BACK VIEW

SELECTOR

 

WARNING:  THE CANDELA SELECT SWITCH MUST BE FIELD SET TO THE REQUIRED CANDELA INTENSITY BEFORE INSTALLATION.  

WHEN CHANGING THE SETTING OF THE CANDELA SELECT SWITCH, MAKE CERTAIN THAT IT “CLICKS” IN PLACE.  AFTER CHANGING 
THE CANDELA SETTING, THE APPLIANCE MUST BE RETESTED TO VERIFY PROPER OPERATION.  IMPROPER SETTING OF THE CANDELA 
SELECT SWITCH, MAY RESULT IN OPERATION AT THE WRONG CANDELA, WHICH COULD RESULT IN PROPERTY DAMAGE AND 
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.  
 

Figure 5: Cover Removal 

 

 

 
 
1.

 

Hold flat screwdriver near the tip and insert the tip about 
1/8” into one of the slots in the cover as shown. 

2.

 

Pull straight down as shown to pop off cover. 

 

 

CAUTION:  

Prying, turning or pivoting with screwdriver in    

order to remove the cover may result in damage to ceiling. 

WARNING:  REMOVAL OF THE COVER AT THE BACK OF THE MOUNTING PLATE COULD RESULT IN SEVERE ELECTRIC SHOCK.

 

WARNING:  THE RSS STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT." 

WARNING:  WHEN INSTALLING STROBES IN AN OPEN OFFICE OR OTHER AREAS CONTAINING PARTITIONS OR OTHER VIEWING 

OBSTRUCTIONS, SPECIAL ATTENTION SHOULD BE GIVEN TO THE LOCATION OF THE STROBES SO THAT THEIR OPERATING EFFECT 
CAN BE SEEN BY ALL INTENDED VIEWERS, WITH THE INTENSITY, NUMBER, AND TYPE OF STROBES BEING SUFFICIENT TO MAKE SURE 
THAT THE INTENDED VIEWER IS ALERTED BY PROPER ILLUMINATION, REGARDLESS OF THE VIEWER'S ORIENTATION.  FAILURE TO 
DO SO COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 

WARNING:  A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON'S FIELD OF VIEW, UNDER 

CERTAIN CIRCUMSTANCES, MIGHT INDUCE A PHOTO-SENSITIVE RESPONSE IN PERSONS WITH  EPILEPSY.  STROBE REFLECTIONS IN A 
GLASS OR MIRRORED SURFACE MIGHT ALSO INDUCE SUCH A RESPONSE.  TO MINIMIZE THIS POSSIBLE HAZARD, WHEELOCK 
STRONGLY RECOMMENDS THAT THE STROBES INSTALLED SHOULD NOT PRESENT A COMPOSITE FLASH RATE IN THE FIELD OF VIEW 
WHICH EXCEEDS FIVE (5) Hz AT THE OPERATING VOLTAGE OF THE STROBES.  WHEELOCK ALSO STRONGLY RECOMMENDS THAT THE 
INTENSITY AND COMPOSITE FLASH RATE OF INSTALLED STROBES COMPLY WITH LEVELS ESTABLISHED BY APPLICABLE LAWS, 
STANDARDS, REGULATIONS, CODES AND GUIDELINES. 
 
NOTE:  

NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation Guidelines in using fewer, higher intensity strobes within the same protected area. 

 

CAUTION:  

Check the installation instructions of the manufacturers of other equipment used in the system for any guidelines or restrictions on wiring and/or 

locating Notification Appliance Circuits (NAC) and notification appliances.  Some system communication circuits and/or audio circuits, for example, may require 
special precautions to assure immunity from electrical noise (e.g. audio crosstalk). 

 

Summary of Contents for RSS-24MCC

Page 1: ...IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS SPECIFICATIONS Table 1 UL ULC Ratings Model Regulated Voltage VDC VRMS Voltage Range Limit Per UL 1971 VDC VRMS Voltage Range Per CAN ULC S526 02 VDC VRMS Strobe Candela cd Mounting Options RSS 24MCC 24 16 0 33 0 20 0 31 0 15 30 75 95 A B C D RSS 24MCCR 24 16 0 33 0 20 0 31 0 15 30 75 95 A B C D NOTES 1 Strobes will produce 1 flas...

Page 2: ...ode NEC Wheelock recommends use of the largest backbox option shown and the use of approved stranded field wires whenever possible to provide additional wiring room for easy installation and minimum stress on the product from wiring FLUSH MOUNTING A STD SINGLE GANG BACKBOX 2 DEEP 6 32 SCREWS STROBE MOUNTING PLATE SMP COVER MAXIMUM NUMBER OF CONDUCTORS AWG 18 AWG 16 AWG 14 AWG 12 4 4 4 4 FLUSH OR S...

Page 3: ...ON AT THE WRONG CANDELA WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND OR OTHERS Figure 5 Cover Removal 1 Hold flat screwdriver near the tip and insert the tip about 1 8 into one of the slots in the cover as shown 2 Pull straight down as shown to pop off cover CAUTION Prying turning or pivoting with screwdriver in order to remove the cover may result in damage to ceil...

Page 4: ...y repair or replacement shall be at Wheelock s sole discretion and shall constitute fulfillment of all obligations under this warranty THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT THE FOREGOING LIMITED WARRANTY SPECIFICALLY EXCLUDES ANY SOFTWARE REQUIRED FOR THE OPERATION OF OR INCLUDED IN A PRODUCT WHEELOCK ...

Reviews: