background image

P82580 B 

Sheet 5 of 8

 

MOUNTING INFORMATION: 

The SA-H5-B and SA-H15-B may be wall mounted by simply using the holes in the swivel base to locate and drill mounting holes.  
For ease of mounting, the swivel base may be removed from the horn body.  Then mount the base to the surface with appropriate 
hardware.  Slots are also provided in the base for banding straps, to allow mounting to beams, poles, and girders.  The mounting base 
is also fully adjustable in both the vertical and horizontal planes.  See Figure 10. 
 

CAUTION:

  These devices are not intended for use in hazardous locations as defined by the National Electrical Code (NEC) and 

by the National Fire Protection Association (NFPA). 
 

Mounting Base 

Figure 10. 

 

 

 

NOTE:  Loosening the wing nut will allow for both pitch and rotation of the unit. 

 

CAUTION:  When adjusting horn position, be careful not to lose adjusting hardware. 

 
 
An interface adapter (mounted to the horn) permits weatherproof connection.  The interface adapter is threaded for standard 1/2" pipe, 
and will accommodate BX cable, flexible or rigid conduit and matching connectors.  If the interface adapter is not suitable for your 
installation, then replace it with the clear plastic shield and 2 short mounting screws packed separately. 
 
 

Figure 11. 

 

 

 

Summary of Contents for SA-H5-B

Page 1: ...unction as a 600 Ohm Audio Page Port i e does not require Talk Battery See Figure 2 NOTE All CAUTIONS and WARNINGS are identified by the symbol All warnings are printed in bold capital letters WARNING...

Page 2: ...n audible NOTE 1 If unused C O port requires talk battery to pass audio most do then a Wheelock Zone Control is required as an interface for zoned paging systems For single zone paging a Wheelock PRM...

Page 3: ...ditional Horn Speakers up to 150 maximum will require the PRM 150 Preamplifier for correct level and impedance matching SPECIFICATIONS Horn Speaker Dimensions 8 15 16 Dia X 10 D Voice Coil Impedance 8...

Page 4: ...sound pressure level Although designed for continuous operation the use of continuous tone signals at high volume is not recommended While short tone bursts should cause no problem sustained operatio...

Page 5: ...devices are not intended for use in hazardous locations as defined by the National Electrical Code NEC and by the National Fire Protection Association NFPA Mounting Base Figure 10 NOTE Loosening the...

Page 6: ...2440 2 Amp Output 4 See Table 6 1 See Table 7 RPS 2440 4 Amp Output 8 See Table 6 3 See Table 7 Table 4 Quantity Of SA H5 B Full Power With RPS 2406 Power Supply Wire Run Wire Awg Feet 24 22 18 16 14...

Page 7: ...possible damage an amplifier with a bass roll off filter horn protect circuit should be used CAUTION Always operate audio amplifiers and speakers within their specified ratings Excessive input may di...

Page 8: ...D RESULTS THERE IS NO WARRANTY AGAINST DAMAGE RESULTING FROM MISAPPLICATION IMPROPER SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN...