P84577 G 

Sheet 7 of 14

 

 

4.3   SP40/2 OPERATION  
 

Refer to the SP40/2 Installation, Operation, Maintenance, and Troubleshooting Manual for proper operation instructions of 
the panel. 

 
5.0   USING THE SP4-APS WITH THE AUDIO BOOSTER (SPB-80/4, SPB-160 and SPB-320) 
 
5.1   MOUNTING INSTRUCTIONS: (SPB-80/4 and SPB-160) 
 

The SP4-APS modules are mounted inside the SPB-80/4 and the SPB-160 enclosures using the Splitter Mounting Bracket 
(SPMB-4Z - purchased separately).   
 
The Splitter Mounting Bracket can be used to mount two SP4-APS modules to the SPB-160 audio booster and one to the 
SPB-80/4.  The bracket is to be mounted over the 24VDC Power Supply.  Figure 9 shows the mounting location of the SP4-
APS Splitter to the Splitter Mounting Bracket (SPMB4Z).   
 

PS

-

PS

+

TB
1

N

L

ADDRESSABLE PAGING 

SPLITTER (SP4-APS)

SPLITTER MOUNTING 

BRACKET (SPMB4Z)

24VDC 

POWER SUPPLY

ZONE

ZONE

IN

+

-

+

-

+

-

EX1 EX2

IN

+

-

OUT

+

-

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 1

ZONE 2

CLASS B

WIRING

CLASS A

WIRING

24 VDC

AUDIO

ALARM

RS 485

TROUBLE

POWER

IN

+

-

OUT

+

-

IN

+

-

OUT

+

-

Z2

Z1

+

-

+

-

Z3

Z4

+

-

+

-

IN

+

-

+

-

+

-

EX1 EX2

IN

+

-

OUT

+

-

ZONE 1

ZONE 2

ZONE 3

ZONE 4

ZONE 1

ZONE 2

CLASS B

WIRING

CLASS A

WIRING

24 VDC

AUDIO

ALARM

RS 485

TROUBLE

POWER

IN

+

-

OUT

+

-

IN

+

-

OUT

+

-

Z2

Z1

+

-

+

-

Z3

Z4

+

-

+

-

 

Figure 9: 

SP4-APS Mounting Location for the SPB-80/4 and SPB-160 

 
Figure 10 shows the correct mounting location. 
 

SPLITTER COVER

SPLITTER PC BOARD

(4) #8-32 KEPS NUT

BACKPLATE

(4) #6-32 SCREW

(4) COVER STANDOFFS

SPLITTER MOUNTING 

BRACKET

(SPMB4Z)

 

Figure 10: 

Mounting Diagram for the SP4-APS Splitter and SPMB-4Z Mounting Bracket 

Summary of Contents for SP4-APS

Page 1: ...SAFEPATH4 system is not in the alarm condition When the SAFEPATH4 system is in the alarm condition all telephone paging and background music inputs are silenced and the emergency message is broadcast on all zones The SP4 APS is used with the Telephone Zone Controller SP4 TZC and controls the distribution of the telephone paging and background music functions NOTE Use of the Telephone Zone Controll...

Page 2: ...an be configured for either CLASS A or CLASS B It cannot do both at the same time The maximum audio power output on any zone is 40 watts Expansion EX1 EX2 terminals follow the Class A or B setting that applies to all zones Instead of speakers up to four SPB 160 or SPB 80 4 or two SPB 320 Audio Boosters may be connected to an audio output zone provided that nothing else is on that zone The total nu...

Page 3: ...LASS B Note that end of line resistors UL Listed 10K Ohm EOLR are required at the end of each audio output zone even if no speakers are present on a zone End of line resistors are required on the EX1 and EX2 connections whether they are used or not Figure 4 shows the SP4 APS set for CLASS B audio field wiring The audio zone outputs are either 25Vrms or 70 7Vrms matching the audio input voltage Rem...

Page 4: ...setting If SW2 is set for CLASS A then all zone outputs and expansion outputs must be wired for CLASS A When using the SP4 APS in CLASS B configuration end of line resistors UL Listed 10K Ohm EOLR must be used at the end of each expansion circuit 3 2 2 24VDC Wiring The SP4 APS requires 24VDC input in order to operate Wire the 24VDC from 24VDC connections on the SP40 2 or the DC OUT connections on ...

Page 5: ...CTING ALL POWER SOURCES TO THIS UNIT FIRST FAILURE TO DO SO MAY RESULT IN DAMAGE TO THE PC BOARDS DISCONNECTING FIRST DISCONNECT BATTERY POWERAT BATTERY TERMINALS THEN DISCONNECTAC POWERAT THE POWER SOURCE RECONNECTING FIRST RECONNECTAC POWERAT THE POWER SOURCE THEN RECONNECT BATTERY POWERAT THE BATTERY TERMINALS WARNING BGM VOLUME SP4 APS MOUNTING STUDS SP40 2 BACKPLANE MOUNTING STUDS COVER STAND...

Page 6: ...W4 J2 W7 W8 P84014 REV ZONES OUT TO SPEAKERS OR UP TO FOUR SPB 160 S OR SPB 80 4 S OR TWO SPB 320 S PER ZONE Power Limited SW1 CC 10K OHM EOLR EXPANSION OUT TO AUDIO BOOSTERS Power Limited CC ALARM INPUT Power Limited 24VDC Power Limited AUDIO Power Limited N L 120VAC INPUT Non Power Limited RUN POWER LIMITED WIRING AWAY FROM NON POWER LIMITED WIRING USING THE KNOCKOUTS ON THE RIGHT SIDE OF THE PA...

Page 7: ...hows the mounting location of the SP4 APS Splitter to the Splitter Mounting Bracket SPMB4Z PS PS TB1 N L ADDRESSABLE PAGING SPLITTER SP4 APS SPLITTER MOUNTING BRACKET SPMB4Z 24VDC POWER SUPPLY ZO N E ZO NE IN EX1 EX2 IN OUT ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 CLASS B WIRING CLASSA WIRING 24 VDC AUDIO ALARM RS 485 TROUBLE POWER IN OUT IN OUT Z2 Z1 Z3 Z4 IN EX1 EX2 IN OUT ZONE 1 ZONE 2 ZONE 3 ...

Page 8: ...above the top and down the right side of the splitter module s EX1 and EX2 are not used when the SP4 APS is connected to an Audio Booster Terminate as follows CLASS A Jumper to and to CLASS B UL Listed 10K Ohm EOLR across each EX zone OUT IN OUT IN OUT IN 24 VDC AUDIO RS 485 ALARM POWER TROUBLE Z1 Z2 Z3 Z4 EX1 EX2 IN CLASS B A SW2 SP4 APS JP1 NAC CC SW1 TB1 TB2 TB7 TB6 TB5 TB4 TB3 JP1 Shorted 70Vr...

Page 9: ... AUD IN J4 J5 AUD2 OPEN AUD2 SHORT D30 D29 TRANSFORMER 25 70 25 70 25 70 25 70 AUDIO INPUT POWER LIMITED AUDIO RETURN POWER LIMITED Battery 1 Battery 2 Battery 4 Battery 3 120VAC INPUT NON POWER LIMITED BATTERY LEADS NON POWER LIMITED PLACE WIRE RUN AT LEAST 1 4 ABOVE THE TOP OF THE CIRCUIT BOARD AND AT LEAST 1 4 FROM POWER LIMITED WIRING 1 ALARM ZONE OUTPUTS AND RS485 POWER LIMITED IN EX1 EX2 IN ...

Page 10: ...30 D29 TRANSFORMER 25 70 25 70 25 70 25 70 Audio Zones Out POWER SUPPLY SW1 NAC EX1 and EX2 are not used when the SP4 APS is connected to an Audio Booster Terminate as follows CLASS A Jumper to and to CLASS B 10K Ohm EOLR across each EX zone 10K Ohm EOLR OUT IN OUT IN OUT IN 24 VDC AUDIO RS 485 ALARM POWER TROUBLE Z1 Z2 Z3 Z4 EX1 EX2 IN CLASS B A SW2 SP4 APS JP1 NAC CC SW1 TB1 TB2 TB7 TB6 TB5 TB4 ...

Page 11: ...P4 Telzone Programmer software See the SP4 TZC installation sheet P84567 for further information 6 1 3 TELEPHONE PAGING MODE Paging Mode occurs when telephone paging commands are sent from the SP4 TZC to the SP4 APS Splitter s via RS 485 digital control signals See Figure 13 for location See the SP4 TZC installation sheet P84567 for further information on the RS485 connections When the addressed S...

Page 12: ...O TROUBLE LEDS NETWORK TROUBLE LEDS RS 485 IN TRB RS 485 OUT TRB GENERAL TROUBLE LED POWER LED Figure 15 SP4 APS Power and Trouble LED Indicators Figure 15 shows the Power and Trouble LED indicators on the SP4 APS PC board 1 Ensure that the green POWER LED is ON If no LED s are lighted check the 24VDC input power 2 Verify that SW1 NAC CC switch is set to the desired position 3 Verify the SW2 CLASS...

Page 13: ...nt SP4 APS s Subsequent SP4 APS s will have the RS485 IN LED ON RS485 OUT Open X RS485 OUT wiring open No communication to subsequent SP4 APS s Subsequent SP4 APS s will have the RS485 IN LED ON 24VDC Wiring Disconnected X All LED indicator will be OFF See Note 2 Ground Fault on any terminal except RS485 X No indication on SP4 APS Trouble LED and Ground Fault LED indicators will light on the SP40 ...

Page 14: ...R SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR FREE OR THAT THE SOFTWARE WILL MEET ANY OTHER STANDARD OF PERFORMANCE OR THAT THE FUNCTIONS OR PERFORMANCE OF THE SOFTWARE WILL MEET THE USER S REQUI...

Reviews: