Provision for room ventilation
This appliance is not connected to a fume exhaust device.
Therefore it must be installed and connected in compliance with current
installation regulations.
Particular attention must be paid to the applicable standards concerning
room ventilation.
Room ventilation
This appliance must only be installed and used in well-ventilated
rooms, in compliance with the current and local regulations, with
openings in the walls or with special ducts enabling adequate
natural or forced ventilation, and ensuring the air necessary for
correct combustion and air change
.
In particular, if there is only this gas appliance in the room, a hood must
be installed above it to ensure natural and direct extraction, with a
straight vertical duct of length equal to at least twice the diameter and a
minimum section of at least 100cm2.
For the inlet of fresh air into the room, a similar opening of at least 100
cm2 directly to the outside must be provided at a suitable height from
the floor so as not to be obstructed on the inside or outside of the wall
and not to hinder the correct combustion of the burners and the regular
extraction of vitiated air, and with a height difference of at least 180cm
with respect to the outlet opening.
The quantity of air necessary for combustion must not be less than 2
m3/h for every kW of power (see total power in kW on the appliance
dataplate).In all other cases, when there are other appliances in the
same room, or when direct natural ventilation is not possible and indirect
natural ventilation or forced ventilation is required, contact a qualified
specialist for carrying out installation and preparing the ventilation
system in strict compliance with the current regulations.
Flues already used by other appliances must not be used for the fume
exhaust.
Prolonged intensive use of the appliance may call for additional ventilation,
for example opening of a window or more effective ventilation, for example
increasing the level of mechanical ventilation where present.
Air inlet section
min. 100 cm2
Air outlet section
min. 100 cm2
Air inlet section
min. 100 cm2
Air inlet section
min. 100 cm2
Electric fan
Cooker hood
flue