5-2
PROBLEM
CAUSE
CORRECTION
Unit will not run - no fan
and no compressor.
1. Unit not turned “ON” or not set dry
enough.
1. Set control to “CONTINUOUS.” This will allow the fan and com-
pressor to run regardless of the ambient humidity.
2. No power to unit.
2a. Power supply cord not plugged in. Plug in cord.
2b. Unit plugged into outlet that has no power to it (blown fuse or
tripped circuit breaker). Advise customer to correct this problem
with a qualified electrician.
3. Bucket In/Water Level switch open.
3a. Empty bucket.
3b. Make sure bucket is installed properly.
3c. Check switch. Replace, if defective.
4. Defective power supply cord or loose
wiring in unit.
4. Check wiring and supply cord. Repair or replace defective parts.
5. Defective humidistat.
5. Run diagnostics. Replace electronic control, if needed.
Fan runs - compressor
does not run.
1. Mechanical Models: Deicer thermostat
open.
2. Electronic Models: Thermistor out of
range or evaporator is less than 30°F.
1a. Let evaporator coil thaw. Normal if coil is frosted over.
1b. Replace deicer thermostat if it is still open after coil thaws and
warmed up.
2a. Unit in defrost mode. Raise room temperature.
2b. Run diagnostics. Replace electronic control, if needed.
3. Compressor overload or relay defective. 3. Check both components and replace, if defective.
4. Compressor windings open.
4. Check continuity and replace if one or both windings are open.
Fan does not run -
compressor runs.
1. Fan motor not getting power.
1. Check wiring. Repair or replace, as necessary.
2. Fan motor defective.
2. Replace fan motor.
3. Fan blade jammed.
3. Remove obstruction. Replace if fan blade is damaged.
Fan and compressor run -
evaporator coil frosted over.
1. Ambient room temperature is too cold
(non deicer model).
1. Turn unit off until room temperature reaches 65°F (18.3°C).
Fan and compressor run -
no dehumidification.
1. Unit out of refrigerant.
1. Follow sweep charge procedure to find and repair leaks.
2. Humidity too low.
2. Turn unit off until humidity goes up.
3. Dirty evaporator or blocked air filter.
3. Clean air filter and/or evaporator.
Unit runs - insufficient
dehumidification.
1. Area is not sealed off - open doors and/
or windows.
1. Isolate area by closing doors and windows.
2. Grilles obstructed.
2. Move unit or items so grilles are not blocked.
3. Dirty evaporator or blocked air filter.
3. Clean air filter and/or evaporator.
4. Low refrigerant charge.
4. Follow sweep charge procedure to find and repair leaks.
5. Unit too small for area being
dehumidified.
5. Close off into smaller area.
TROUBLESHOOTING
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating.
Failure to do so can result in death or electrical shock.
Summary of Contents for AD25BSS
Page 4: ... iv NOTES ...
Page 8: ...1 4 NOTES ...
Page 28: ...3 12 NOTES ...
Page 33: ...6 1 WIRING DIAGRAM 1 WIRING DIAGRAMS ...
Page 34: ...6 2 WIRING DIAGRAM 2 ...
Page 35: ...6 3 WIRING DIAGRAM 3 ...
Page 36: ...6 4 NOTES ...
Page 37: ...6 5 NOTES ...
Page 38: ...6 6 NOTES ...
Page 40: ...CORPORATION ...