background image

18

Select the best location
Location for Installing Indoor Unit

• Where there is no obstacle near the air outlet

and air can be easily blown to every corner.

• Where piping and wall hole can be easily

arranged.

• Observe the required distance from ceiling and

wall according to the wiring diagram.

• Where the air filter can easily be removed.
• Keep the unit and remote control 1m or more

from television, radio etc.

• To prevent the effects of a fluorescent lamp,

keep the unit as far as possible from it.

• Do not put anything near the air inlet that could

obstruct it.

• In a place that can bear the weight and will not

increase operating noise and vibrations.

Location for Installing Outdoor Unit

• Install in a convenient and well-ventilated place.
• Avoid installing it where flammable gas could

leak.

• Observe the required distance from the wall.
• The distance between Indoor and outdoor unit

should be 5 meters and can go up to maximum
15 meters with additional refrigerant charge.

• Do not install the outdoor unit in a dirty or

greasy place, near a vulcanization gas exit.

• Avoid installing it at the roadside where it could

be soiled with muddy water.

• A fixed base where operating noise will not

increase.

• Where the air outlet is not obstructed.

Model

Max. Allowable

Tubing Length at

Shipment (m)

Limit of Tubing

Length (m)

Limit of Elevation

Difference H (m)

Required amount

of additional

refrigerant (g/m)

7K~24K

5

15

5

20

Indoor unit

Pipe length is 
15 meters Max.

Outdoor unit

Height should 

be less than 5m

Outdoor unit

Pipe length is
15 meters Max.

Indoor unit

Height should be less 

than 5m

Downloaded from AC-Manual.com Manuals

Summary of Contents for AMD 011

Page 1: ...a qualified technician in compliance with the producer s instructions and following local safety norms Do not repair or replace any parts of the appliance unless it is specifically written in the user instructions The grounding of this appliance is compulsory Make sure that the power supply cord is long enough to allow the right connection Do not use any extension cord for power supply Do not pull...

Page 2: ...ent potentially negative consequences for the environment and for human health The symbol on the product or on the documents accompanying the product indicates that this appliance should not be treated as household waste but must be given to the appropriate local gathering place where electric and electronic appliances are stored and recycled SAFEGUARDING THE ENVIRONMENT AIR CONDITIONER PRECAUTION...

Page 3: ... Horizontal Adjustment Louver 9 Air Filter 10 Remote Control Outdoor unit 11 Air Intake 12 Pipes and Power Connection Cord 13 Drain Hose Note Condensate water drains at COOLING or DRY operation 14 Air Outlet Images in the user instructions are based on external views of standard models shape and design vary according to the model Downloaded from AC Manual com Manuals ...

Page 4: ...uring sleep mode Filter monitor indicator 5 Filter monitor indicator flashes after 240 hours of usage as reminder to clean the filter After filter cleaning press the reset button located on the indoor unit behind the front panel in order to interrupt the flashing of the filter monitor indicator Emergency ON OFF button 6 Used to control the unit by pressing the button when the RC is out of work Use...

Page 5: ...select fan speed in sequence auto high medium or low 9 SWING BUTTON Used to stop or start vertical adjustment louver swinging and set the desired up down airflow direction 10 JET BUTTON Used to start or stop the fast cooling Fast cooling operates at high fan speed with 18 C set temp automatically 10 6 5 3 2 1 4 9 8 7 INDICATOR SYMBOLS ON RC DISPLAY Cooling indicator Dry indicator Fan only indicato...

Page 6: ...han 3 minutes all presetting will be cancelled and timer will display Zero How to remove the batteries Remove the battery cover in the direction of the arrow Press the positive pole of the battery softly with your fingers then draw the batteries out of the compartment All this should be done by adults children are forbidden to remove the batteries from the remote control in order to avoid danger o...

Page 7: ...ton is ineffective in this case 3 Setting temperature Press once to raise temperature setting by 1 raise C Press once to lower temperature setting by 1 lower C Note Heating mode is NOT available for cooling only models 4 Turning on Press button when the appliance receives the signal the RUNNING indicator of the indoor unit lights up During mode changes wait a few seconds and repeat the operation i...

Page 8: ...G button again when the louvers swing to a suitable angle as desired Horizontal airflow control with hands Turn the control rods of the horizontal adjustment louvers to change horizontal air flow as shown Note The shape of the unit may look different from that of the air conditioner you have selected A Do not turn the vertical adjustment louvers manually otherwise malfunction may occur If that hap...

Page 9: ...ture Operation mode Target temperature 21 C or below HEATING 22 C 21 C 23 C FAN ONLY 23 C 26 C DRY Room temperature decrease 1 5 C after operating for 3 minutes Over 26 C COOLING 26 C Indoor temperature Operation mode Target temperature 26 C or below DRY Room temperature decrease 1 5 C after operating for 3 minutes Over 26 C COOLING 26 C Your feeling button adjustment procedure Uncomfortable becau...

Page 10: ...ge Note Heating is NOT available for cooling only air conditioner JET mode JET mode is used to start or stop fast cooling Fast cooling operates at high fan speed changing the set temperature automatically to 18 C JET mode can be set when the appliance is in operation In JET mode you can set airflow direction or timer If you want to quit from JET mode press any JET MODE FAN ON OFF or TEMPERATURE SE...

Page 11: ...ing the next operation after 9 5 hours 1 Set desired operating mode temperature and indoor fan speed then press the TIMER button h flashes on display 2 Point the remote control at the signal receptor of the indoor unit press the or button when h flashes Choose the time you desire then press the TIMER button a beep can be heard A Timer indicator on the indoor unit lights up B h stops flashing Press...

Page 12: ...r filter 1 Open the front panel 2 Press the handle of the filter gently 3 Slide out the filter 2 Cleaning and refitting the air filter If the filter is very dirty clean it with a solution of lukewarm water and neutral detergent After cleaning let it dry 3 Close the front panel Fig A Fig B PROTECTION Operating condition The protective device maybe trip and stop the appliance in the cases listed bel...

Page 13: ...device or fuse blown Please wait for 3 minutes and start again protection device may be preventing unit to work Are the RC batteries low Is the plug not properly plugged No cooling or heating air Is the air filter dirty Are the intakes and outlets of the air conditioner blocked Is the temperature set properly Ineffective control Has there been a strong interference from excessive static electricit...

Page 14: ...national wiring standards by authorized service people only Distance from wall should be over 50mm Distance from ceiling should be over 50mm Distance from floor should be over 2000mm Distance from the wall should be over 50mm Air intake distance from the wall should be over 250mm Air intake distance from the wall should be over 250mm Air outlet distance from the wall should be over 500mm Over 250m...

Page 15: ...nient and well ventilated place Avoid installing it where flammable gas could leak Observe the required distance from the wall The distance between Indoor and outdoor unit should be 5 meters and can go up to maximum 15 meters with additional refrigerant charge Do not install the outdoor unit in a dirty or greasy place near a vulcanization gas exit Avoid installing it at the roadside where it could...

Page 16: ...d outside Install a sleeve through the wall hole to keep the wall tidy and clean 3 Indoor Unit Piping Installation Fit the piping liquid and gas pipe and cables through the wall hole from outside or fit them from inside after completing indoor piping and cables connections so as to connect to outdoor unit Decide whether saw off the plastic part in accordance with the piping direction as shown belo...

Page 17: ...ed to the drain pipe make sure to be thermally insulated when passing it through the indoor unit When the piping is directed to the right piping power cord and drain pipe should be thermally insulated and fixed at the rear of the unit with a piping fixer A Insert the pipe fixer to the slot B Press to hook the pipe fixer onto the base Thermal insulation Wrapped with vinyl type Large pipe Thermally ...

Page 18: ...om the unit by loosening the screw Connect the wires to the terminals on the control board individually as follows 2 Secure the power connecting cord on the control board with cable clamp 3 Refit the access door in the original position and tighten the screw 4 Use a recognized circuit breaker for 24K model between the power source and the unit A disconnecting device to adequately disconnect all su...

Page 19: ... sectional area Type Normal cross sectional area 7K 9K 12K H05VV F 1 0 1 5mm X3 H07RN F 1 0 1 5mm X3 H05RN F 0 75mm X2 Heat pump To indoor 18K H05VV F RVV 1 5 2 0mm X3 H07RN F 1 5mm X3 H05RN F 0 75mm X2 Heat pump To indoor 24K H07RN F 2 5mm X3 H07RN F 1 5mm X3 Heat pump 1 5mm X4 Cooling only H05RN F 0 75mm X3 Heat pump To outdoor Make sure that the colour of wires of the outdoor unit and the termi...

Page 20: ...pped with a wrapping tape and the connector should be put inside the unit Defrost wire indoor Defrost wire outdoor HEAT PUMP power connecting cord 1 power connecting cord Indoor unit Terminal Outdoor unit Terminal Brown Blue Brown Blue Brown Blue Brown Blue Yellow Green Yellow Green N L L 1 L 1 L 3 L 3 L 2 L 2 N N L L HEAT PUMP Power connecting cord 1 Power connecting cord Indoor unit Terminal Out...

Page 21: ...alve Connect the pipes to the 2 way and 3 way valves separately according to the required torque 4 Outdoor Unit Cable Connection see previous page Air purging Air containing moisture remaining in the refrigeration cycle may cause a malfunction on the compressor After connecting the indoor and outdoor units evacuate air and moisture from refrigerant cycle using a vacuum pump as shown below Note Bec...

Page 22: ...er There must be an air break switch After installing the consumer must operate the air conditioner correctly according to this manual keep a suitable storage for maintenance and move of the air conditioner in the future Type of fuse used on indoor unit controller is Φ 5x20 with rating 2 5A 250V or 3 15A 250V Caution Mount with the lowest moving parts of indoor unit at Least 2 4m above floor or gr...

Reviews: