11
Application Table
Model
Mode
Thermostat Terminals
X = Energized Terminal
Control Board Taps
Cool
Heat
HUM
EM
W1
O
Y2/Y1
G
A
B
C
D
A
B
C
D
CFM CFM CFM CFM CFM CFM
CFM
CFM
WEFV08S -1A
Cont. Blower
X
500
400
375
375
Cooling
**
X
X
1000 800
700
600
Heating
X
1000 800
700
600
Aux. Heat***
X
X
***
***
***
***
1000
800
700
600*
Emer. Heat***
X
X
***
***
***
***
1000
800
700
600*
WEFV12S-1A
Cont. Blower
X
600
500
400
350
Cooling
**
X
X
1200 1000 800
600
Heating
X
1200 1000 800
600
Aux. Heat***
X
X
***
***
***
***
1200 1100* 1100* 1100*
Emer. Heat***
X
X
***
***
***
***
1200 1100* 1100* 1100*
WEFV14M-1A
Cont. Blower
X
750
700
600
500
Cooling
**
X
X
1500 1400 1200 1000
Heating
X
1500 1400 1200 1000
Aux. Heat***
X
X
***
***
***
***
1500 1400 1200* 1200*
Emer. Heat***
X
X
***
***
***
***
1500 1400 1200* 1200*
WEFV16M-1A
Cont. Blower
X
900
800
750
700
Cooling
**
X
X
1800 1600 1500 1400
Heating
X
1800 1600 1500 1400
Aux. Heat***
X
X
***
***
***
***
1800 1700 1600* 1500*
Emer. Heat***
X
X
***
***
***
***
1800 1700 1600* 1500*
WEFV20L-1A
Cont. Blower
X
1000 950
900
800
Cooling
**
X
X
2000 1900 1800 1600
Heating
X
2000 1900 1800 1600
Aux. Heat***
X
X
***
***
***
***
2000 1800
1700
1700
Emer. Heat***
X
X
***
***
***
***
2000 1800
1700
1700
*This CFM is not approved for use with highest kW heater size.
**Humidistat will reduce cooling airflow by 10% in high humidity.
***Airflow is the greater of the COOL and HEAT values when both electric heat and heat pump are operating.
NOTES:
Adjust tap (+) will increase airflow by 10%, while tap (-) will decrease airflow by 12%.
Adjust tap test will cause the motor to run at 70% of full airflow. Use this for troubleshooting only.
At the start of a call for cooling there is a short run at 82% of airflow for 7.5 minutes.
At the end of a call for cooling there is a blower delay of 1 minute.