11
Cooling Only—2-Stage Heat—Outdoor Thermostat Enabled
NOTES:
■
1
st
Stage enabled through room thermostat.
■
2
nd
Stage enabled through closed outdoor thermostat.
1. Y/Y2 enables high speed fan cooling.
2. E/W1 enables low speed fan heating. W/W2 with outdoor
thermostat closed enables high speed fan heating.
3. OT1 PJ4 must be cut for this configuration.
4. OT2 PJ2 must be cut for this configuration.
5. Cut HUM PJ6 jumper if using humidistat. Humidistat opens
on humidity rise.
6. DIP Switch 4 must be in the “ON” position.
WMAHV Heat Pump with Single- or 2-Stage Heating and Options for Emergency Heat
Heat Pump—1-Stage Emergency Heat and 1-Stage Auxiliary Heat
NOTES:
1. Y enables high speed fan cooling.
2. E and W2 enable high speed fan heating.
3. If OT2 PJ2 jumper is cut, E and W2 enable low speed fan
heating.
4. Cut HUM PJ6 jumper if using humidistat. Humidistat opens
on humidity rise.
5. DIP Switch 4 must be in the “ON” position.
Goodman 6 Long
HIGH VOLTAGE!
WARNING
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
OT2
HUM
N
O
PI
D
F
F
O
YCON
CONDENSER
R
E\W1
OUTDOOR
THERMOSTATS
HEATPUMP
W1
OT1
COM
O
W2
W2
ED
W/W2
O
OTC OT1
W1
W2
H
C
TI
W
S
HEATER
C
R
24 VAC
OT2
C
R
Y1
W1
W2
C
R
G
Y1
HUM
HUMIDISTAT
Y/Y2
G
Y
PN B1368274
See Note 3
See Note 4
See Note 5
If Needed
Please refer
to manual
for proper
DIP switch (CFM)
configuration.
Humidistat
(Optional)
Condensing Unit
Outdoor Thermostat
Room Thermostat
2
nd
Stage Heater
1
st
Stage Heater
See Note 5
To Comfort Alert
Module (If Used)
If Needed
Please refer
to manual
for proper
DIP switch (CFM)
configuration.
Humidistat
(Optional)
Room Thermostat
1
st
Stage Heater
See Note 4
Remove
Production
Wire Y1-O
See Note 3
See Note 4
Heat Pump