Confirm the entire suction line from the evaporator unit to the condensing unit is insulated using cellular
insulation or equivalent. Seal all seams with Armaflex 520 Foam Insulation Adhesive or equivalent.
•
Confirm that the control is displaying the correct temperature and that no alarms are present.
INSTALLING THE CONDENSING UNIT(continued)
Finalizing the Installation
Approximate Operating Pressures
(Cellar temperature 55°F)
Low Side PSI
High Side PSI
Temp.
60°F
75
°F
85
°F
95°F
23-2
7
PSIG
25-29 PSIG
105-110
PSIG
26-30 PSIG
135-140
PSIG
152-157
PSIG
27-31 PSIG
82
-
87
PSIG
Page 37
08/04/21