Page 8
23835-1-0607
Mantel Chart (Figure 3)
Figure 3
Clearances (Figure 4)
Clearance from top front edge of fireplace to ceiling is 36"
Clearance from side of fireplace to adjacent sidewall is 6".
36”
(914mm)
6” (152mm)
Figure 4
MANTEL
19”
18 3/4”
17”
16”
15”
14”
13”
12”
11”
10”
2 1/4”
1 1/2”
3/4”
8”
6”
4 1/2”
3 3/4”
3”
12” (305mm)
10” (254mm)
TOP EDGE OF FIREPLACE
COMBUSTIBLE TRIM AND MANTELS
ALLOWED IN SHADED AREA
Figure 5
Note:
Island (C) and Room Divider (F)
installation is possible as long as the
horizontal portion of the vent system
(H) does not exceed 20 feet with a
minimum vertical run of 8 feet. See
details in Venting Section.
When you install your Direct Vent
Fireplace in (F) Room divider or (A) Flat
on wall corner positions, a minimum of
6 inches clearance must be maintained
from the perpendicular wall and the
front edge of the appliance.
Figure 2
Combustible Material
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the fireplace. The flow of heat can
ignite combustibles.
(A) CORNER
INSTALLATION
(E) ANGLED CORNER
INSTALLATION
(C) ISLAND
INSTALLATION
(B) CABINET
INSTALLATION
(F) ROOM DIVIDER
INSTALLATION
(D) FLUSH WALL
INSTALLATION
Clearance to Combustibles
Back
0" (0 mm)
Side
0" (0 mm)
Floor
0" (0 mm)
Top Stand-off
0" (0 mm)
Top Framing Edge
6" (152 mm)
CLEARANCES
LOCATING FIREPLACE