Page 31
15628-0-0903
1.
Spark ignitor will not light pilot after repeated depressing
of piezo ignitor button.
a. Defective ignitor (no spark at electrode) - Check for spark
at electrode and pilot; if no spark and electrode wire is
properly connected, replace ignitor.
b. No gas or low gas pressure.
- Check remote shut off valves from fireplace. Usually
there is a valve near the main. There can be more than one
(1) valve between the fireplace and main.
- Low pressure can be caused by a variety of situations
such as a bent line, too narrow diameter of pipe, or low
line pressure. Consult with plumber of gas supplier.
c. No LP in tank.
- Check LP (propane) tank. Refill tank.
2.
Pilot will not stay lit after carefully following lighting
instructions.
a. Defective thermocouple.
- Check that pilot flame impinges on thermocouple.
Clean and/or adjust pilot for maximum flame
impingement.
- Ensure that the thermocouple connection at the gas
valve is fully inserted and tight (hand tight plus 1/4 turn)
faulty themopile if reading is below specified minimum.
- Disconnect the thermocouple from the valve, place one
millivolt meter lead wire on the tip of the thermocouple
and the other meter lead wire on the thermocouple copper
lead. Start the pilot and hold the valve knob in. If the
millivolt reading is less than 15 mv, replace the
thermocouple.
b. Defective valve.
- If thermocouple is producing more than 15 millivolts,
replace faulty valve
3.
Pilot burning, no gas to burner, valve knob "ON", on/off
switch "ON."
a. "On/Off" switch, wall switch, or wires defective.
- Check "on/off" switch and wires for proper connections.
Place jumper wires across terminal at switch - if burner
comes on, replace defective switch. If OK, place jumper
wires across switch wires at gas valve-if burner comes on,
wires are faulty or connections are bad.
b. Thermopile may not be generating sufficient milli-voltage.
- If the pilot flame is not close enough physically to the
thermopile, adjust the pilot flame.
- Be sure the wire connections from the thermopile at the
gas valve terminals are tight and the thermopile is fully
inserted into the pilot bracket.
- Check the thermopile with a millivolt meter. Take the
reading at TH-TP & TP terminals of the gas valve. The
meter should read 325 millivolts minimum, while holding
the valve knob depressed th the pilot position, with the
pilot lit, and the ON/OFF switch in the OFF position.
Replace the faulty thermopile if the reading is below the
specified minimum.
-With the pilot in the ON position, disconnect the
thermopile leads from the valve. Take a reading at the
thermopile leads. The reading should be 325 millivolts
minimum. Replace the thermopile if the reading is below
the minimum.
c. Defective valve.
- Turn valve knob to "ON." Place ON/OFF switch to
"ON." Check with millivolt meter at thermopile terminals.
Millivolt meter should read greater than 100 M.V. If the
reading is okay and the burner does not come, replace the
gas valve.
d. Plugged main burner orifice.
- Check main burner orifice for blockage, clean main
burner orifice.
4.
Frequent pilot outage problem.
a. Pilot flame may be too high or too low, or blowing (high),
causing pilot safety to drop out.
- Clean and adjust flame for maximum flame impingement
on the thermocouple. Follow lighting instructions
carefully.
5.
The pilot and main burner extinguish while in operation.
a. No LP (Propane) in tank.
- Check LP (Propane) tank. Refill fuel tank.
b. Inner vent pipe leaking exhaust gases back into system.
- Check for leaks.
c. Glass too loose, gasket leaks in corners after usage.
- Be certain glass assembly is installed correctly and
tighten corner.
d. Horizontal vent improperly pitched.
- The horizontal vent cap should slope down only enough
to prevent any water from entering the unit. The maximum
downwards slope is 1/4 inch.
e. Bad thermopile or thermocouple.
- Replace if necessary.
f. Improper vent cap installation.
- Check for proper installation and freedom from debris
or blockage.
6.
Glass soots.
a. Flame impingement on logs.
- Adjust the log set so that the flame does not excessively
impinge on it.
b. Improper air shutter adjustment.
- Adjust the air shutter.
7.
Flame lifts off main burner.
a. Insufficient oxygen being supplied.
- Check to make sure vent cap is installed properly and
free of debris. Make sure that vent system joints are tight
and have no leaks.
- Check to make sure that no material has been placed at
the burner base.
- Be sure glass is tightened properly on unit, particularly
on top corners.
TROUBLESHOOTING
With proper installation and maintenance, your new Direct Vent Fireplace should provide years of trouble-free service. If you do
experience a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis
of problems and the corrective action to be taken.