W4413

Regulating Presence Detector with photocell

Note: COMAHP required for commissioning 

                             

Installation and Commissioning Instructions

COMRED & COMREY

 

   

June 2016 - Rev F

Summary of Contents for COMRED

Page 1: ...W4413 Regulating Presence Detector with photocell Note COMAHP required for commissioning Installation and Commissioning Instructions COMRED COMREY June 2016 Rev F...

Page 2: ...g screw so that approximately 3mm of thread is visible and then twisting the detector off the back box Note the arrow symbol moulded into the bottom of the back box The fixing holes allow for mounting...

Page 3: ...within a control circuit will not affect the operation of those lights that remain powered and under the control of the detector When switching via the relay output multiple detectors relay outputs ma...

Page 4: ...N Sensitivity This is an approximation and should be tested on site during commissioning Like all programmable parameters the sensitivity settings will be retained in the event of a power failure and...

Page 5: ...ocell DISABLED If the photocell is configured as DISABLED for relay Switching Control it will have no effect on the control of that load which will be ON continuously during periods of occupancy unles...

Page 6: ...ts off makes another measurement and stores the value in SET POINT LOW The lights now switch on again to acknowledge a successful programming operation The two switching thresholds have now been set a...

Page 7: ...rgets 4 Please note that although configurable as a regulating photocell closed loop dimming according to daylight due to the probable corner of roomlocation where there will be excessive influence by...

Page 8: ...IMUM RECOMMENDED MOUNTING HEIGHT 3 5m RANGE Adjustable up to 20m OFF DELAY 1 min 96 hours plus 10 second walk test mode PHOTOCELL Passive Active Regulating adjustable 50 5000 lux MATERIAL Flame retard...