Battery low voltage
Threshold for "Battery low" alarm (see no. 9 in section 6.4.2).
Default Value
Range
Resolution
5 V
5 … 58 V
0.1 V
Unit
LCD name
Modbus address
Volts
Bat. low U
0x1014
10
Battery deep discharge voltage
Threshold for the "Battery deep discharged" alarm (see no. 10 in section 6.4.2).
Default Value
Range
Resolution
5 V
5 … 58 V
0.1 V
Unit
LCD name
Modbus address
Volts
Bat. deep disch. U
0x1015
11
Battery max. discharge current
During backup the UPS module limits the maximum discharge current to this value reducing the out-
put voltage if necessary.
Default Value
Range
Resolution
21 A
5 … 21 A
0.1 A
Unit
LCD name
Modbus address
Amperes
Bat. max. disch. I
0x1016
12
Battery capacity – Supercap capacitance
Nominal capacity (Ah) of the installed battery or capacitance (F) in case a Supercapacitor is installed.
This parameter is used to calculate the battery State of Charge (SoC) during charge and discharge.
Default Value
Range
Resolution
1 Ah or 1 F
1 … 200 Ah or F
0.1 Ah or F
Unit
LCD name
Modbus address
Ampere hours or Farad
Bat. capacity
0x1017
13
Battery min. temperature
Threshold for the "Battery undertemperature" alarm (see no. 3 in section 6.4.2).
Default Value
Range
Resolution
-40 °C
-40 … 60 °C
1 °C
Unit
LCD name
Modbus address
Degree Celsius
Bat. min. T
0x1018
14
Battery max. temperature
Threshold for the "Battery over temperature" alarm (see no. 4 in section 6.4.2).
Default Value
Range
Resolution
60 °C
-40 … 60 °C
1 °C
Unit
LCD name
Modbus address
Degree Celsius
Bat. max. T
0x1019