Battery lifetime
Threshold for the "Battery lifetime elapsed" alarm (see no. 5 in section 6.4.2).
Default Value
Range
Resolution
100 kh
1 … 100 kh
1 kh
Unit
LCD name
Modbus address
Kilo hours
Bat. lifetime
0x101A
16
Ri alarm mode
Mode of operation for the "Battery Ri too high" alarm (see no. 2 in section 6.4.2).
Default Value
Values (Modbus value)
Disabled
Disabled (0), Fixed (1), Automatic (2), Auto. Done (3)
Unit
LCD name
Modbus address
N/A
Ri mode
0x101B
17
Ri nom.
Used for the threshold calculation of the "Battery Ri too high" alarm (see no. 2 in section 6.4.2).
Default Value
Range
Resolution
1 m©
1 … 300 m©
0.1 m©
Unit
LCD name
Modbus address
Milli Ohm
Ri nominal
0x101C
18
Ri max. variation
Used for the threshold calculation of the "Battery Ri too high" alarm (see no. 2 in section 6.4.2).
Default Value
Range
Resolution
300%
50 … 300%
1%
Unit
LCD name
Modbus address
Percent
Ri max. variation
0x101D
19
Operating mode
Defines the UPS module's operating mode. See section 5.1 and 5.2 for details of each mode.
Default Value
Values (Modbus value)
UPS
UPS (1), DC/DC (2)
Unit
LCD name
Modbus address
N/A
Operating mode
0x1020
20
Nominal output voltage
UPS mode:
The UPS module enters backup mode when the output voltage drops below 90% of the
nominal value. It is also the regulated output voltage during backup.
DC-DC mode:
The UPS module corresponds to the regulated output voltage.
Default Value
Range
Resolution
10 V
10 … 58 V
0.1 V
Unit
LCD name
Modbus address
Volts
Output nominal U
0x1021