6
|
User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
28
21
Max. input current
UPS mode:
The UPS module limits the maximum input current to this value reducing the battery
charging current if necessary.
DC-DC mode:
The UPS module limits the maximum input current (in DC-DC mode the input is con-
nected to the battery connection) to this value reducing the output voltage if necessary.
Default Value
Range
Resolution
20 A
1 … 21 A
0.1 A
Unit
LCD name
Modbus address
Amperes
Max input I
0x1022
22
Max. output current
The UPS module limits the maximum output current to this value reducing the output voltage if neces-
sary.
Default Value
Range
Resolution
20 A
5 … 21 A
0.1 A
Unit
LCD name
Modbus address
Amperes
Max output I
0x1023
23
Max. Backup time enable
If enabled, the UPS module shuts down if the backup last more than the "Max. backup time" value
Default Value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
Backup time enable
0x1024
24
Max. backup time
If "Max. Backup time enable" field is enabled, the UPS module shuts down if the backup last more
than the specified amount of time.
Default Value
Range
Resolution
1440 min
1 … 1440 min
1 min
Unit
LCD name
Modbus address
Minutes
Back. time max
0x1025
25
Buzzer enable
Enable/Disable buzzer sound in case of alarm.
Default Value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
Buzzer enable
0x1026