6
|
User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
30
31
Aux enable
Enable/Disable auxiliary output.
Default Value
Values (Modbus value)
Enabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
Aux enable
0x102C
32
Cold start on inhibit toggle
Enable/Disable the cold start on inhibit toggle. See section 5.1.6 for more details.
Default Value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
CS on inhibit
0x102D
33
Cold start on battery connection
Enable/Disable the cold start on battery connection. See section 5.1.6 for more details.
Default Value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
CS on battery
0x102E
34
PC shutdown enable
See section 5.1.5 for more details.
Default Value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
PC shutdown enable
0x1030
35
PC automatic restart enable
See section 5.1.5 for more details.
Default Value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
PC restart enable
0x1031
36
PC shutdown delay
See section 5.1.5 for more details.
Default Value
Range
Resolution
3600 s
1 … 3600 s
1 s
Unit
LCD name
Modbus address
Seconds
PC shutdown delay
0x1032