6
|
User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
31
37
PC shutdown time
See section 5.1.5 for more details.
Default Value
Range
Resolution
600 s
1 … 600 s
1 s
Unit
LCD name
Modbus address
Seconds
PC shutdown time
0x1033
38
PC restart minimum time
See section 5.1.5 for more details.
Default Value
Range
Resolution
1 s
1 … 60 s
1 s
Unit
LCD name
Modbus address
Seconds
PC restart time
0x1034
39
PC off detection current threshold
See section 5.1.5 for more details.
Default Value
Range
Resolution
0 A
0 … 20 A
0.1 A
Unit
LCD name
Modbus address
Amperes
PC OFF I
0x1035
40
PC off detection timer
See section 5.1.5 for more details.
Default Value
Range
Resolution
1 s
1 … 60 s
1 s
Unit
LCD name
Modbus address
Seconds
PC OFF time
0x1036
41
Blink output on backup enable
See section 5.1.7 for more details.
Default Value
Values
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
Blink out enable
0x1040
42
Blink output on backup Ton
See section 5.1.7 for more details.
Default Value
Range
Resolution
10 s
10 … 600 s
1 s
Unit
LCD name
Modbus address
Seconds
Blink out Ton
0x1041