6
|
User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
32
43
Blink output on backup Toff
See section 5.1.7 for more details.
Default Value
Range
Resolution
0.2 s
0.1 … 60 s
0.1 s
Unit
LCD name
Modbus address
Seconds
Blink out Toff
0x1042
44
Output short circuit latch enable
When enable the device disables the output when a short circuit is detected on the output. To restart
the output, the operator must press the OK button on the front panel.
Default Value
Values
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
Seconds
Out SC latch enable
0x1043
45
Output short circuit detection voltage threshold
See section 5.1.7 for more details.
Default Value
Range
Resolution
3 V
3 … 58 V
0.1 V
Unit
LCD name
Modbus address
Volts
Out SC detection th.
0x1044
46
High inrush load enable
When enabled and the output is switched on, the unit sends a higher current pulse to withstand loads
with a high start-up inrush current.
Default Value
Values
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
N/A
High inrush enable
0x1045
47
Battery installation date
This field is used to compute the battery lifetime. If the battery lifetime exceeds the "Battery lifetime"
value (see no. 15 in section 6.2), the "Battery lifetime elapsed" alarm activates (see no. 5 in section
Default Value
Range
1st January 2000
from 1st January 2000 to 31st December 2099
Unit
LCD name
Modbus address
N/A
Bat. installation date
0x1100
48
Battery charge cycles
The value increments automatically at the end of a battery charge cycle.
Default Value
Range
Resolution
0
0 … 65535
1
Unit
LCD name
Modbus address
Cycles
Bat. charge cycles
0x1104