6
|
User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
25
3
Modbus parity
The parity for Modbus over RS485 serial port. Available values are None, Even, Odd.
Default Value
Values (Modbus value)
Even
None (1), Even (2), Odd (3)
Unit
LCD name
Modbus address
N/A
Modbus parity
0x1002
4
Modbus stop bits
The parity for Modbus over RS485 serial port.
Default Value
Range
Resolution
1
1, 2
1
Unit
LCD name
Modbus address
N/A
Modbus stop bits
0x1003
5
Battery type
Defines the type of battery connected to the device. See section 5.1.3 for details about the different
charging algorithms.
Default Value
Values (Modbus value)
Pb
Lead (1), Nickel (2), Lithium (3), SuperCap (4)
Unit
LCD name
Modbus address
N/A
Bat. type
0x1010
6
Battery charge voltage
The maximum voltage applied to the battery while charging. See section 5.1.3 for details about the
use of this parameter on the different charging algorithms.
Default Value
Range
Resolution
10 V
10 … 58 V
0.1 V
Unit
LCD name
Modbus address
Volts
Bat. charge U
0x1011
7
Battery charge current
The maximum current sourced to the battery while charging. See section 5.1.3 for details about the
use of this parameter on the different charging algorithms.
Default Value
Range
Resolution
0.5 A
0.5 … 20 A
0.1 A
Unit
LCD name
Modbus address
Amperes
Bat. charge I
0x1012
8
Battery float voltage
The maximum voltage applied to the battery once it is fully charged. See section 5.1.3 for details about
the use of this parameter on the different charging algorithms.
Default Value
Range
Resolution
10 V
10 … 58 V
0.1 V
Unit
LCD name
Modbus address
Volts
Bat. Float U
0x1013