6
|
User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
36
11
Auxiliary output disabled
Active if the auxiliary output is disabled in settings.
LCD name
Modbus address
Aux disabled
0x4027
Value 1
Value 2
Inactive (0), Active (1)
Not used
6.4.2
Alarms
1
Battery disconnect
Active when no battery is detected by the UPS module.
LCD name
Modbus address
Bat. disconnected
0x4010
Value 1
Value 2
Inactive (0), Active (1)
Not used
2
Battery Ri too high
Active when measured battery internal resistance exceeds the alarm threshold (see section 5.1.2).
LCD name
Modbus address
Bat. Ri too high
0x4011
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Max. measured value
3
Battery undertemperature
Active when the battery measured temperature (using the optional external sensor) is under the
threshold specified in "Battery min. temperature" field (see no. 13 in section 6.2). If active, the battery
charged is disabled.
LCD name
Modbus address
Bat. under temperature
0x4012
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Min. measured value
4
Battery overtemperature
Active when the battery measured temperature (using the optional external sensor) exceeds the
threshold specified in "Battery max. temperature" field (see no. 14 in section 6.2). If active, the battery
charged is disabled.
LCD name
Modbus address
Bat. over temperature
0x4013
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Max. measured value