User interface
Wieland Electric GmbH | BA001052 (Rev. A) | 11/2018
38
11
Backup
Active when the system is in backup (see section 5.1.1).
LCD name
Modbus address
Backup
0x4030
Value 1
Value 2
Inactive (0), Active (1)
Not used
12
Input undervoltage
Active when the measured input voltage is under 90% of the "Nominal output voltage" field (see no.
LCD name
Modbus address
Input under voltage
0x4031
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Min. measured value
13
Input overvoltage
Active when the measured input voltage exceeds 120% of the "Nominal output voltage" field (see no.
LCD name
Modbus address
Input over voltage
0x4032
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Max. measured value
14
Output undervoltage
Active when the measured output voltage is under 90% of the "Nominal output voltage" field (see no.
20 in section 6.2).
LCD name
Modbus address
Output under voltage
0x4033
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Min. measured value
15
Output overvoltage
Active when the measured output voltage exceeds 120% of the "Nominal output voltage" field (see
LCD name
Modbus address
Output over voltage
0x4034
Value 1
Value 2
Inactive (0), Active (1)
Status 0
→
1: Offending threshold
Status 1
→
0: Max. measured value
16
Output overload
Active when the measured output current reaches the threshold specified in "Max. output current"
field (see no. 22 in section 6.2).
LCD name
Modbus address
Output overload
0x4035
Value 1
Value 2
Inactive (0), Active (1)
Not used