Operating instructions (Translation) 

flare

 TIME M4-1/M4-2  

81.020.0000.0 / 81.020.0001.0

 

flare

 TIME M8-1/M8-2  

81.020.0002.0 / 81.020.0003.0 

Multi-mode, multi-range timer 

Wieland Electric GmbH 
Brennerstraße 10-14 
96052 Bamberg 
Tel.:  +49 (951) 9324-0 
Fax:  +49 (951) 9324-198 
Internet: www.wieland-electric.com 
Email: info@wieland-electric.com 

 

 

Doc. # 

BA000825

 - 03/2016 (Rev. E) 

flare TIME M4-1/M4-2/M8-1/M8-2 

EN

 

 

 

N O T I C E  

Personnel which installs, programs, operates or maintains this device must have read and 
understand these instructions. 

 

W A RN I N G 

 

The personnel must be thoroughly familiar with all warnings, notes and procedures de-
scribed in these operating instructions. 

 

Where necessary, safety precautions and safety devices must comply with the applicable 
regulations. 

 

Damaged products must neither be installed nor put into operation. In case of a defect, 
please return the device to Wieland Electric. 

 

Connect or disconnect only when de-energized! 

 

The device may not be opened. 

 

Do not introduce any objects into the unit! 

 

Keep away from fire and water! 

1

 

Controls and functional elements 

flare TIME M8-1 

8 functions / B1 

flare TIME M8-2 

8 functions / B1 

flare TIME M4-1 

4 functions 

flare TIME M4-2 

4 functions 

 

 

 

 

 

 

 

 

 

 

1–Timebase selector,  2–user label, 3

time setting selector, 4–LED OUT (orange), 

5–LED Power (green), 6–operating mode selector, 7–INST/TIME (R2) selector 

2

 

Dimensions and wiring 

 

Wiring notices 

 

Use solid wire (2.5 mm

2

 max.) or ferrules 

with insulative sleeves to connect to the 
terminals. 
To maintain the withstand voltage after 
connecting the terminals, insert no more 
than 8 mm of exposed conductor into the 
terminal 

 

Recommended screw tightening torque: 
0,49 Nm 

3

 

Switching functions 

Notices 

 

The supply voltage (contacts A1-A2) must be present in order to be able to activate switch-
ing functions. For the flare TIME M4-1 and flare TIME M4-2, closing the contacts A1-A2 
initiates the timing action directly. 

 

Contact B1 activates the timing action for the flare TIME M8-1 and M8-2 models. 

 

In the operating position of the relay the orange LED lights constantly. (2) 

 

Turn off the power supply of the module (contacts A1/A2) before you select another time 
function 

 

If you change the time factor or the time basis during operation, the timing action – with 
delay if applicable – is interrupted and the switching function continues with the new elapse 
time. 

Switching functions explained: 

For model flare TIME M4-1 and 2 there is no input B1. The function of the timing relay is 
activated when the power (A1-A2) is turned on. 

A–ON delay 

Input B1/A2 is ignored while the timer is in 
operation. 

B–Flicker OFF start

 

 

Input B1/A2 is ignored while the timer is in 
operation. 

C–Single shot and OFF delay 

Input B1/A2 is valid while the timer is in 
operation. 

B2–Flicker ON start 

 

Input B1/A2 is ignored while the timer is in 
operation. 

D–OFF delay 

 

Input B1/A2 is valid while the timer is in 
operation. 

E–Single shot 

 

Input B1/A2 is valid while the timer is in 
operation. 

G–ON/OFF delay 

 

Input B1/A2 is valid while the timer is in 
operation. 

J–ON delayed single shot, fixed time 

 

Input B1/A2 is valid while the timer is in 
operation. 

4

 

Technical Data 

Input circuit

Input circuit

Input circuit

Input circuit 

 

Rated voltage A1-A2; B1-A2 

24…240

 

V AC/DC  

Voltage range 

20.4…264 V AC/DC 

Input frequency 

50/60 Hz 

Power consumption 240 V AC 

M4-1/M8-1 

 

M4-2/M8-2 

4.5 VA 
6.6 VA 

Power consumption 24V DC 

M4-1/M8-1 

 

M4-2/M8-2 

1.1 W 
1.2 W 

Reset voltage 

10 % of rated voltage 

Power OFF time for resetting by power off-on  min. 0.1 s 
Voltage input 

H level 

 

L level 

20.4 to 264 V AC/DC 
0 to 2.4 V AC/DC 

Input signal duration at B1 

min. 100 ms 

Insulation resistance A1-A2-B1 / contacts 

min. 100 M

 at 500 V DC 

Dielectric strength between input circuit and 
output terminal 

2000 V AC (50/60 Hz, for 1 min) 

Timer circuit

Timer circuit

Timer circuit

Timer circuit 

 

Operating modes 

M4-1/M4-2 

 

M8-1/M8-2    

4 // A, B2, E, J (see switching functions) 
8 // A, B, C, B2, D, E, J, G

 

Operating mode relay 2 

INIT 

 

TIME    

synchronous to supply voltage 
time controlled output

 

Time ranges    

0.1s, 1s, 10s, 1min, 10min, 1h, 10h, 100h

 

Time range setting    

max. 12 × time range (0 to 12) 

3)

 

Accuracy of operating time    

max. ±1% of full scale

 

Setting error    

max. ±10 % of full scale ± 0.05 s 

 

Minimum input signal width    

50 ms (start input)

 

Influence of voltage    

max. ±0.5 % of full scale

 

Influence of temperature    

max. ±2 % of full scale

 

Output circuit

Output circuit

Output circuit

Output circuit    

4

44

4

 

 

Contacts 

M4-1/M8-1 

 

M4-2/M8-2 

one changeover contact 
two changeover contacts 

Rated operating voltage 

 

24…240

 

V AC/DC 

DC ripple 

 

20 % 

Contact load (contact output) 

5 A at 250 V AC (ohmic load, cos 

φ

 = 1) 

5 A at 24 V DC (ohmic load) 

Contact output minimum load 

10 mA at 5 V DC (P level, reference value) 

Output switching capacity 

see diagram "Load limiting curve" below 

Life cycle 

min. 100.000 operations (5 A at 250 V AC, 
ohmic load, 360 operations/h) 

General data

General data

General data

General data 

 

Installation dimensions 

see figure 

Installation orientation 

any 

Ambient operating temperature 

20 to 55 °C (no icing) 

Storage temperature 

40 to 70 °C (no icing) 

Operating humidity 

25…85 % 

IP rating 

IP20 

Approval 

cURus, LR 

 

Load limiting curve

 as relation 

between ambient operating tempera-
ture and installation pitch when 
installing horizontally. 

Testing method: Supply voltage 240 V 
AC, installation pitch between timers 
0.5, 10 and 50 mm 
 
T

MAX

: Maximum ambient operating 

temperature according to specifica-
tions 

 
 

 

 

                                                                                   

3)

 The accuracy is greatest between ‘9’ and ‘12’, please adjust the time setting selector (1) 

accordingly. Avoid settings between ‘0’ and ‘1’ due to the inaccuracy. 
Setting ‘0’ has a special meaning: With setting ‘0’, sequence checks can immediately be 
performed. The outputs then behave as instantaneous contacts. 

4)

 If the INST/TIME switch (models M4-2/M8-2) is set to INST, relay R2 will operate as instanta-

neous contact and will turn on and off synchronously to the power supply. 