gesis LON R-56/0 (RC)
16
Wieland Electric | BA000580 | 6/2009 (Rev. A)
4.5
Technical Data
Wireless technology
Technology
Use of the EnOcean protocol
Frequency band
868.3 MHz
Range
– Line of sight
Typically 30 m in corridors; up to 100 m in halls
– Plasterboards / wood
Typically 30 m through max. five walls
– Brick/aerated concrete walls Typically 20 m through max. three walls
– Reinforced concrete
walls/ceilings:
Typically 10 m through max. one ceiling
Significant restriction of the range (up to shielding
of the radio signal):
Insulation wool on metal foil, suspended ceilings or elevated floors and
panels made of metal or carbon fibre, lead glass or glass with metal coating,
steel furniture, mounting of the switch on metal. Fire protection walls, lift shafts.
Stairways, supply and similar areas should be sealed off. The angle at which the radio
signals meet a wall also has a role to play. The effective wall thickness and, therefore, the
signal attenuation will vary depending on the angle. Where possible, the signals should
meet a wall at a slight angle; wall alcoves should be avoided.
Bus connection
Connection type
Connection cross-section
Screw clamp terminals
0.14 to 4
mm², single-core
0.14 to 2.5
mm², finely stranded
6.5
mm stripped in each case
Operating voltage
12,5
V DC ( -15
%/+10%) SELV
Rated current
80
mA
Antenna connection
SMA socket
Impedance
50
Ω
Antenna
suitable for 868.3 MHz; the
Wieland antenna is recommended; see ordering instruc-
tions
Electrical safety
Protection class
none (depends on subsequent work)
Degree of protection
IP 00; according to installation in gesis distribution box:
min IP20
Degree of soiling
2
Surge voltage category
III
EMC requirements
conforms to EN 61000-6-2/-6-3 and EN 50090-2-2
Operating conditions
Field of application
For installation in gesis distribution boxes, which are in
turn intended for fixed installation in interior and dry areas
Temperature ranges
– Operating environment
−
5 °C to 45 °C
– Storage
−
25 °C to +70 °C
relative humidity
5% - 93%
Moisture condensation
not permitted
Climate resistance
according to EN 50090-2-2
General data
Housing material
Plastic, halogen and phosphorous-free
Housing colour
black
Behaviour in fire
V2 according to UL 94 (housing)
Thermal load
approx. 3 kWh
Approval
L
ON
M
ARK
-compliant
Weight
approx. 110
g
Dimensions
see "Dimensions, Connections and Function Elements"
CE marking
according to EMC Directive (residential and functional
buildings), Low Voltage Directive