Wieland
podis
system
Manual V 1.03 / ref. no. 00.000.0059.0 / 28.03.2001
Supply load
Rated operating voltage
400 V 3~AC
±
10%
Rated operating current I
c
3.3 A
(50°C, switching capacity AC~3)
System frequency of input
47 … 63 Hz
Supply electronics
Input voltage
24 V DC
±
20%
Residual ripple
max. 5% residual ripple
Input current
< 2 A
Nominal consumption
approx. 5 W + max. 12 W
per digital output (max. 24 W)
Motor feeder connector
Nominal capacity per motor
max. 1100 W
Rated load voltage (phase voltage)
400 V 3~AC
Min./max. load current
0.5 A / 3.3 A
Overload protection
Current monitoring
Braking contactor
400 V AC, max. 1 A
High-speed contact
400 V AC, 1 A (normally open contact,
closes when the brake is released,
opens when the brake is disconnected)
Field bus connection
Field bus system
PROFIBUS DP / CANLOCAL
Bus connection – PROFIBUS DP
M12 circular connector with metal
housing (socket contact on bus coupler)
Insulation voltage
Field bus / electronics
500 V DC (by DC/DC converter
and
optocoupler)
Electronics / motor starter
2.5 kV AC (by optocoupler in motor starter)
Diagnostic and extension bus
Number of extension modules
max. 4
Type of connection
M12 circular connector
Digital I/Os
Connections of initiators/actuators
M12 circular connector
(4 sockets, each with 5 contacts on
device)
Number of inputs and outputs
6 x IN and 2 x IN/OUT
Inputs
Nominal voltage U
H
24 V DC
±
20%
Residual ripple
max. 5%
Voltage level ”1”
+15 V … +28.8 V DC
Voltage level ”0”
0 V … + 5 V DC
Power consumption at HIGH level
typ. 6 mA per digital input
Concurrence 50%
Signal delay
< 100
µ
s
Outputs
Rated output voltage
24 V
±
20%
Output current
max. 0.5 A per output
(short-circuit-proof)
General data
Ambient temperature
0° … +40°C (50°C derating)
Storage temperature
-25° … +55°C
Connection type of input (flat cable)
podis CON
Connection type of output
podis CON
(motor connector)
Wire range
2.5 mm
2
(flat cable)
Mounting location
As required
Type of protection
IP 65
Relative humidity (Class F
10 … 95%
according to DIN 40040)
(no moisture condensation)
Air pressure during operation
680 … 1060 hPa
CE mark
Yes
Approvals (in preparation)
UL, CSA, VDE
Norms
UL 508; VDE 0660
Weight approx.
9.2
kg
EMC
Emission
EN 55011:1998/A1 1999 Class A Group 1
Immission EN
50082-2/03.95
Industry
EN 61000-4-2:1995 (ESD)
EN 61000-4-4:1995 (Burst)
EN 61000-4-5:1995 (Surge)
EN 61000-4-6:1996
(incl. HF fields, mains-borne)
EN 61000-4-11:1994 (voltage dips)
Technical data
Motor control unit MRC