Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
•
05/2006
- 17 -
5.1 Setup flow chart
MODE
PV/SV display mode
OUT
/
OFF
(Approx. 1s)
Control output OFF
function [
] (*1)
Output manipulated
variable
MODE
(Approx. 3s)
MODE
▲
+ MODE
▼
+ MODE (Approx. 3s)
[Main setting mode] [Sub setting mode] [Auxiliary function setting mode1]
SV 1
[ ]
AT
setting/Auto-reset
setting [
/
]
Setting value lock
selection [
]
MODE MODE
MODE
SV 2
[
]
OUT1 proportional
band setting [ ]
SV high limit setting
[
]
MODE MODE
MODE
OUT2 proportional
band setting [
]
SV low limit setting
[
]
MODE
MODE
Integral time setting
[ ]
Sensor
correction
setting [
]
MODE
MODE
Derivative time setting
[ ]
Communication
protocol [
]
MODE
MODE
ARW setting
[ ]
Instrument
number
setting [
]
MODE
MODE
OUT1 proportional
cycle setting [ ]
Data
transfer
rate
selection [
]
MODE
MODE
OUT2 proportional
cycle setting [
]
Heater
burnout
Alarm
setting [
. ]
Parity
selection
[
]
MODE
MODE
MODE
A1 setting
[
]
Loop break Alarm
action time [
]
Stop bit selection
[
]
MODE
MODE
MODE
A2 setting
[
]
Loop break alarm
action span [
]
MODE
MODE
•
▲
+
MODE
: Press
the
MODE
key, while the
▲
key is being pressed.
•
▼
+
MODE
(Approx. 3s):
Press the
MODE
key for approx. 3s, while the
▼
key is being pressed.
•
▲
+
▼
+
MODE
(Approx. 3s): Press the
MODE
key for approx. 3s, while the
▲
and
▼
keys are being pressed.
•
Dotted lines show options, which are indicated only when the options are applied.
(*1) If Auto/Manual control function is selected in the
OUT
/
OFF
key function selection, even though the
OUT
/
OFF
key is
pressed, control output OFF function does not work, but manual control is selected.