Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
•
05/2006
- 7 -
1.2 Rated input
Input type
Input range
Resolution
–200 ... 1370 °C
–320 ... 2500 °F
1 °C (°F)
K
–199.9 ... 400.0 °C
–199.9 ... 750.0 °F
0.1 °C (°F)
J
–200 ... 1000 °C
–320 ... 1800 °F
1 °C (°F)
R
0 ... 1760 °C
0 ... 3200 °F
1 °C (°F)
S
0 ... 1760 °C
0 ... 3200 °F
1 °C (°F)
B
0 ... 1820 °C
0 ... 3300 °F
1 °C (°F)
E
–200 ... 800 °C
–320 ... 1500 °F
1 °C (°F)
T
–199.9 ... 400.0 °C
–199.9 ... 750.0 °F
0.1 °C (°F)
N
–200 ... 1300 °C
–320 ... 2300 °F
1 °C (°F)
PL-
0 ... 1390 °C
0 ... 2500 °F
1 °C (°F)
C(W/Re5-26)
0 ... 2315 °C
0 ... 4200 °F
1 °C (°F)
–199.9 ... 850.0 °C
–199.9 ... 999.9 °F
0.1 °C (°F)
Pt100
–200 ... 850 °C
–300 ... 1500 °F
1 °C (°F)
–199.9 ... 500.0 °C
–199.9 ... 900.0 °F
0.1 °C (°F)
JPt100
–200 ... 500 °C
–300 ... 900 °F
1 °C (°F)
4 … 20 mA DC
–1999 ... 9999
(1)(2)
1
0 … 20 mA DC
–1999 ... 9999
(1)(2)
1
0 … 1 V DC
–1999 ... 9999
(1)
1
0 … 5 V DC
–1999 ... 9999
(1)
1
1 … 5 V DC
–1999 ... 9999
(1)
1
0 … 10 V DC
–1999 ... 9999
(1)
1
(1) For DC input, input range and decimal point place can be changed.
(2) Connect
50