14033590.01 10/2014 GB/D
WIKA operating instructions model CS4S
15
GB
6.1 Mounting
Mount the instrument individually in a vertical control panel, in order to fulfil the
specification with respect to mounting protected from dust and sprayed-water (Ingress
protection IP 66).
Test the rigidity of the control panel and check the case for damage. If the material of the
control panel is not rigid enough or a damage is present at the case, the compliance with
ingress protection IP 66 cannot be guaranteed.
Control panel thickness for installation: 1 ... 15 mm
Max. installation height: 2,000 m
First, insert the controller into the control panel, from the front. Then attach the screw
bracket into the slots on top and bottom housing and tighten.
WARNING!
In order to avoid any damage to the plastic housing, do not tighten the screw
bracket too tightly (max. torque: 0.12 Nm).
WARNING!
If several controllers are to be mounted side-by-side, see 4.3.1 “Panel
cutouts”.
6. Commissioning, operation