WIKA operating instructions model CS4S
GB
7. Configuration
HYh
OUT1 hysteresis with
ON
/
OFF
control mode
■
Input of the hysteresis of control output 1 with
ON
/
OFF
control mode
■
Only available with
ON
/
OFF
control mode.
■
Setting range: 0.1 ... 100.0 °C (°F)
with current/voltage signal input, 1 ... 1,000
1.0 °C
cAcF
OUT2 control mode
■
Selection of the control mode for control output 2
■
Not available if the option 2, control output [DT2] is not present, or if
ON
/
OFF
control
mode is set for control output 2.
■
Selection:
AIr
Selection: (air cooling, linear characteristic)
oIL
(Oil cooling, 1.5-times linear characteristic)
8AF
(Water cooling, 2-times linear characteristic)
Air cooling
oLHb
OUT2 maximum output power
■
Input of the maximum output power for control output 2
■
Not available if the option 2, control output [DT2] is not present, or if
ON
/
OFF
control
mode is set for control output 2.
■
Setting range: OUT2 minimum output power to 100 %
100 %
oLLb
OUT2 minimum output power
■
Input of the minimum output power for Control Output 2
■
Not available if the option 2, control output [DT2] is not present, or if
ON
/
OFF
control
mode is set for control output 2.
■
Setting range: 0 % to OUT2 maximum output power
0 %
db
Overlap band/deadband
■
Setting of the overlap band/deadband for control outputs 1 and 2.
+ Setting value: deadband
– Setting value: overlap band
■
Not available with
ON
/
OFF
control mode or if the option 2, control output [DT2] is
not present.
■
Setting range: -100.0 ... +100.0 °C (°F)
with current/voltage signal input: -1,000 ... 1,000
0 °C
HYhb
OUT2 hysteresis with
ON
/
OFF
control mode
■
Input of the hysteresis for control output 2 with
ON
/
OFF
control mode
■
Only available if the option 2, control output [DT2] is present and if
ON
/
OFF
control
mode is set.
■
Setting range: 0.1 ... 100.0 °C (°F)
with current/voltage signal input: 1 ... 1,000
1.0 °C
AL1F
Alarm type alarm 1 (A1)
■
Setting of the alarm type for alarm 1 (A1)
■
Selection:
no alarm
----
Process high alarm
Ah
High alarm
H
Process low alarm
rAh
Low alarm
L
High alarm with standby
H 8
High/Low alarm
HL
Low alarm with standby
L 8
Range alarm
8Id
High/Low alarm with standby
HL8
no alarm
AL2F
Alarm type alarm 2 (A2)
■
Setting of the alarm type for alarm 2 (A2)
■
Only available when the options [2AS] or [2AL] are present.
■
The alarm types are identical with those of alarm 1 (A1).
no alarm
A1LA
Switch behaviour, alarm 1 (A1)
■
Selection of the switch behaviour for alarm output 1 (A1)
(Relay activated/deactivated on alarm)
■
Not available when “no alarm” is selected as alarm type for alarm 1 (A1).
■
Selection:
noAL
(activated)
rE8h
(deactivated)
activated