14033590.01 10/2014 GB/D
30
WIKA operating instructions model CS4S
GB
h82
SV2 display settings
■
Select whether set point 2 (SV2) is displayed or not.
■
Only available when the option [SV2] is available.
■
Selection:
on
displayed
oFF
not displayed
not displayed
EoUF
Output status with input overshoot
■
Selection of the output status for control output 1 (OUT1) with too high or too low
input value.
■
Only available with current signal control output (4 ... 20 mA) in conjunction with
current/voltage signal input
■
Selection:
oFF
(output OFF)
on
(output ON)
Output OFF
AAnU
Functionality of
OUT
/
OFF
key
■
Setting of the functionality for the
OUT
/
OFF
key
■
Selection:
oFF
Switching off the control output (OFF function)
AAnU
Switching between automatic/manual control
OFF function
Sensor correction
Corrects the input signal of the connected sensor.
If the sensor cannot be placed at the point where control is desired, it is possible that the
measured temperature differs from the temperature to be controlled. When using several
controllers there can be differences in the measured values of the individual controllers,
caused by tolerance variations in the sensors used. In these cases, using the sensor
correction, an alignment can be made. Furthermore, it is possible to compensate for
deviations in the temperature sensor, which have been detected during a calibration.
Switch behaviour, activated (open-circuit principle, no) or deactivated (closed-
circuit principle, nc)
■
Activated (open-circuit principle)
When the control LED of an alarm lights up (ON), the alarm output (between terminals
3-4 or 3-5) is short-circuited (ON, relay activated).
When the control LED of an alarm goes out (OFF), the alarm output is interrupted (OFF,
relay deactivated).
■
Deactivated (closed-circuit principle)
When the control LED of an alarm lights up (ON), the alarm output is interrupted (OFF,
relay deactivated). When the control LED goes out (OFF), the alarm output is short-
circuited (ON, relay activated).
7. Configuration