WIKA operating instructions model CS4S
GB
3. Specifications
Display
Actual value
7-segment LED, 4-digit, red, digit height 10.2 mm
Set point
7-segment LED, 4-digit, green, digit height 8.8 mm
Scale range
-1999 ... 9999
Input
Number and type
1 multi-function input for resistance thermometers, thermocouples and
standard signals
Input configuration
Selectable via terminal connections and menu-driven programming
Resistance thermometer Pt100, JPt100, 3-wire
max. permissible resistance per connecting cable: 10 Ω
Thermocouples
■
Types K, J, R, S, E, T, N, PL-II, C (W/Re5-26)
max. permissible external resistance: 100 Ω
■
Type B
max. permissible external resistance: 40 Ω
Standard signals
0 ... 20 mA, 4 ... 20 mA:
Input impedance 50 Ω (external instrument shunt)
0 ... 1 V:
Input impedance > 1 MΩ
0 ...5 V, 1 ... 5 V, 0 ... 10 V:
Input impedance > 100 kΩ
Measuring time
250 ms
Control outputs
Control output 1
3 different versions are possible
Relay contact
Loading: AC 250 V, 3 A (resistive load), AC 250 V, 1 A (inductive load,
cos ϕ = 0.4)
Logic level
DC 0/12 V, max. 40 mA (short-circuit proof)
for the control of an electronic switch relay (solid-state relay, SSR)
{analogue current signal}
4 ... 20 mA, max. load 550 Ω
Control output 2
1)
For “three-step control”
Output
Contact-free relay, loading: AC 230 V, 0.3 A (resistive load)
Proportional band
0.0 to 10.0 times the proportional band of control output 1
Integral time
Identical to the integral time of control output 1 (see “Control Mode”)
Derivative time
Identical to the derivative time of control output 1 (see “Control Mode”)
Cycle time
1 ... 120 s
Overlap band/deadband
Resistance thermometers and thermocouples: -100.0 ... 100.0 °C
Standard signals: -1,000 ... 1,000 (with a scaling of the input with one
decimal point, this is taken over by the hysteresis).
{ } Items in curved brackets are optional extras for an additional price
1) A combination of alarm output 2 or heater burnout alarm with relay output 2 is not possible.