11116552.11 EN/DE/FR/ES 03/2022
23
WIKA operating instructions pressure transmitter, models E-10 and E-11
EN
Specifications
Load in Ω
Output signal 4 ... 20 mA
≤ (supply voltage - 10 V) / 0.02 A
Output signal DC 0 ... 5 V
> maximum output signal / 1 mA
Output signal DC 0.5 ... 4.5 V
> 100k
Output signal DC 1 ... 5 V
> 100k
Output signal DC 0 ... 10 V
> maximum output signal / 1 mA
Voltage supply
Supply voltage
→ See product label
Max. power consumption
1 W
Dynamic behaviour
Settling time per IEC 61298-2
≤ 2 ms
≤ 10 ms
For model E-10 with measuring range ≤ 0 ... 25 bar at medium temperature < -30 °C
[-22 °F]
For model E-11
Short-circuit resistance
S+ vs. U-
Reverse polarity protection
U+ vs. U-
Insulation voltage
DC 500 V
Material (wetted)
Model E-11 and E-10 with
measuring range ≤ 25 bar
Stainless steel
Model E-10 with measuring range
> 25 bar, NACE-compliant
■
Stainless steel
■
Elgiloy
Sealing
→
See “Process connection”
Material (in contact with the environment)
Case
Stainless steel
Cable
→
See “Electrical connection”
9. Specifications