28
6 Set up with the display and adjustment module
WIKA Operating Instructions - Process pressure transmitter IPT-1*
1. Push the
[OK]
button in the measured value display, the menu
overview is displayed.
2. Confirm the menu "
Basic adjustment
" with
[OK]
, the menu item
"
Units of measurement
" will be displayed.
3. Activate the selection with
[OK]
and select the requested unit with
[->]
(in the example m).
4. Confirm with
[OK]
, the submenu "
Density unit
" appears.
Unit of measurement
Density unit
▶
kg/dm³
pcf
5. Select the requested unit, e.g. kg/dm³ with
[->]
and confirm with
[OK]
, the submenu "
Density
" appears.
Unit of measurement
Density
0001000
kg/dm³
6. Enter the requested density value with
[->]
and
[+]
, confirm with
[OK]
and move to position correction with
[->]
.
The adjustment unit is thus switched over from bar to m.
Proceed as follows to select the temperature unit:
3)
1. Activate the selection with
[OK]
and select "
Temperature unit
with
[->]
.
2. Activate the selection with
[OK]
and select the requested unit with
[->]
(e.g. °F).
3. Confirm with
[OK]
.
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1. Activate in the menu item "
Position correction
" the selection with
[OK]
.
Position correction
Offset
P
=
+0000 mbar
53 mbar
2. Select with
[->]
, e.g. to accept actual measured value.
Position correction
Accept current measured
value?
▶
Accept
Edit
3. Confirm with
[OK]
and move to min.(zero) adjustment with
[->]
.
Proceed as follows:
1. Edit the % value in the menu item "
Min. adjustment
" with
[OK]
.
Carry out a position cor-
rection
Carry out min. adjustment
3)
Selection options: °C, °F.