Operating Instructions Temperature Indicating Controller CF1M
V1.
1
•
03/200
5
- 8 -
Output ON/OFF action hysteresis setting
• Sets the ON/OFF action hysteresis of control output.
• This setting item is available only for the ON/OFF action.
• 0.1 to 100.0°C
1.0°C
Event output function selection
• One of the functions is selectable from Temperature alarm,
Loop break alarm or Heater burnout alarm.
• Heater burnout alarm can be selected only when option [W1X] is
applied.
• Temperature alarm output
:
Loop break alarm output
:
Heater burnout alarm output (option):
Temperature alarm action selection
• Selects temperature alarm action.
• No alarm
:
High limit alarm
:
High limit alarm w/standby
:
Low limit alarm
:
Low limit alarm w/standby
:
High/Low limits alarm
:
High/Low limits alarm w/standby
:
High/Low limit range alarm
:
High/Low limit range alarm w/standby :
Process high alarm
:
Process high alarm w/standby
:
Process low alarm
:
Process low alarm w/standby
:
No alarm
Temperature alarm energized/deenergized selection
• Sets the temperature alarm output as energized or deenergized.
• This setting item is not available if Temperature alarm output
is not selected in Event output function selection, nor if No alarm is
selected in Temperature alarm action selection.
• Energized :
Deenergized :
Energized
Temperature alarm hysteresis setting
• Sets hysteresis value for temperature alarm.
• This setting item is not available if Temperature alarm output is not
selected in Event output function selection, nor if No alarm is selected
in Temperature alarm action selection.
• 0.1 to 100.0°C
(°F)
1.0°C
(°F)
Temperature alarm delayed timer setting
• Sets the action delayed timer for temperature alarm.
Alarm output works past the setting time after the input value
reaches the alarm output range.
• This setting item is not available if Temperature alarm output is not
selected in Event output function selection, nor if No alarm action
is selected in Temperature alarm action selection.
• 0 to 9999 seconds
0s
Main setting value rising rate setting
• Sets the rising rate of main setting value. (Rising value per minute)
• 0 to 9999°C /min. (°F /min.)
With decimal point, 0.0 to 999.9°C /min. (°F /min.)
0°C /min.
Main setting value falling rate setting
• Sets the falling rate of main setting value. (Falling value per minute)
• 0 to 9999°C /min. (°F /min.)
With decimal point, 0.0 to 999.9°C /min. (°F /min.)
0°C /min.