WIKA Operating Instructions Temperature Transmitter T53
T53.10.0IS
Class I, Zone O, Ex ia IIC or Ex iaD, FISCO
P
o
< 0.84 W P
o
< 1.3 W FISCO systems FISCO systems
U
i
30 VDC
30 VDC
17.5 VDC
15 VDC
l
i
120 mA DC 300 mA DC 250 mA DC
P
i
0.84 W
1.3 W
2.0 W
L
i
1 µH
1 µH
1 µH
1 µH
C
i
2.0 nF
2.0 nF
2.0 nF
2.0 nF
T1 ... T4 T
a
≤ 85 °C
T
a
≤ 75 °C
T
a
≤ 85 °C
T
a
≤ 85 °C
T5
T
a
≤ 70 °C
T
a
≤ 65 °C
T
a
≤ 60 °C
T
a
≤ 60 °C
T6
T
a
≤ 60 °C
T
a
≤ 45 °C
T
a
≤ 45 °C
T
a
≤ 45 °C
T53.10.0IS
Class I, Zone 1, Ex ib IIC, FISCO
P
o
< 0.84 W
FISCO systems
U
i
30 VDC
17.5 VDC
l
i
250 mA DC
P
i
5.32 W
L
i
1 µH
1 µH
C
i
2.0 nF
2.0 nF
T1 ... T4
T
a
≤ 85 °C
T
a
≤ 85 °C
T5
T
a
≤ 75 °C
T
a
≤ 75 °C
T6
T
a
≤ 60 °C
T
a
≤ 60 °C
Installation instructions
The sensor circuit is not infallibly galvanically isolated from the Field-
bus input circuit. However, the galvanic isolation between the circuits
is capable of withstanding a test voltage of AC 500 V during 1 minute.
In a potentially explosive gas atmosphere, the transmitter shall be
mounted in an enclosure in order to provide a degree of protection of
at least IP 20 according to EN 60 529.