7.4.2 Possible installation methods with the marking II 1/2 Ex ib IIC T6 Ga/Gb or
II 1/2 D Ex ib IIIC T65 °C Da/Db
The sensor or thermowell tip protrudes into Zone 0. The housing or connection head is in
Zone 1 (Zone 21) or Zone 2 (Zone 22). It is sufficient to use an Ex ib type circuit.
Zone separation is guaranteed if sufficiently-tight (IP67) process connections are used.
Examples of suitable process connections include gas-tight standardised industrial flanges,
threaded connections or pipe connections.
The welded parts, process connections, compression fittings, thermowells or housings
used must be designed such that they withstand all influencing variables resulting from the
process, such as temperature, flow forces, pressure, corrosion, vibration and impacts.