EN
WIKA operating instructions model TR36
14331645.02 07/2021 EN/DE/FR/ES
29
Output signal (4 ... 20 mA version)
Factory configuration
Measuring range
Measuring range 0 ... 150 °C [32 ... 302 °F]
Other measuring ranges are adjustable
Current values for error
signalling
Configurable in accordance with NAMUR NE 043
downscale < 3.6 mA (3.5 mA)
upscale > 21.0 mA (21.5 mA)
Current value for
sensor short-circuit
Not configurable in accordance with NAMUR NE 043
downscale ≤ 3.6 mA (3.5 mA)
Communication
Info data
Tag no., description and user message can be stored
in transmitter
Configuration and
calibration data
Permanently stored
Configuration software
WIKAsoft-TT
→ Configuration software (multilingual) as a download
from www.wika.com
Voltage supply
Supply voltage U
B
DC 10 ... 30 V
Supply voltage input
Protected against reverse polarity
Permissible residual
ripple of supply voltage
10 % generated by U
B
< 3 % ripple of the output
current
Time response
Switch-on delay,
electrical
Max. 4 s (time before the first measured value)
Warm-up time
After approx. 4 minutes, the instrument will function to
the specifications (accuracy) given in the data sheet.
12. Specifications