9. Diagnostic functions
9. Diagnostic functions
Requirement
: Display and operating unit fitted.
9.1 Simulations
9.1.1 Performing a pressure simulation
A pressure value within the measuring range must be entered and is converted into a
current value and output.
1.
Open the operating menu with [↵].
Select “Diagnostic” and confirm with [↵].
2.
Select “Simulation” and confirm with [↵].
3.
Select “Press. simu.” and confirm with [↵].
4.
Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
»
Simulation is active.
5.
Ending the simulation. Press [ESC] to do this.
9.1.2 Performing a current simulation
The selected or entered current value will be simulated and output as the PV (primary
value).
1.
Open the operating menu with [↵].
Select “Diagnostic” and confirm with [↵].
2.
Select “Simulation” and confirm with [↵].
3.
Select “Current sim.” and confirm with [↵].
4.
Select the current value or define via “Input”.
Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
»
Simulation is active.
5.
Ending the simulation. Press [ESC] to do this.