44
WIKA operating instructions process transmitter, model UPT-2x
14111166.02 04/2015 EN/DE
EN
9. Diagnostic functions
9.2 Display/reset drag pointer
The drag pointer function indicates the limit values reached since the last reset. These
limit values can be displayed and reset.
9.2.1 Drag pointer P
min
/ P
max
Displays the minimum and maximum pressure that has occurred since the last reset.
Displays
1.
Open the operating menu with [↵].
Select “Diagnostic” and confirm with [↵].
2.
Select “Drag pointer” and confirm with [↵].
3.
Select “P min/max” and confirm with [↵].
4.
Select “display” and confirm with [↵].
»
Limit values are displayed.
P
▼
= P
min
P
▲
= P
max
Resetting
1.
Open the operating menu with [↵].
Select “Diagnostic” and confirm with [↵].
2.
Select “Drag pointer” and confirm with [↵].
3.
Select “P min/max” and confirm with [↵].
4.
Select “reset” and confirm with [↵].
5.
Select limit value and confirm with [↵].
■
P
▼
= P
min
■
P
▲
= P
max
»
Limit value is reset.