47
WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
11. Detail setup
11.7
Setting the HART
communication
11.7.1
Setting the short address (multidrop mode)
Setting range:
0 ... 63
1.
Open the operating menu with [↵].
Select “Detail setup" and confirm with [↵].
2.
Select “HART” and confirm with [↵].
3.
Select “Short addr.” and confirm with [↵].
4.
Change digit using [▲] [▼] and confirm with [↵]. The
cursor moves to the next digit. Repeat for each digit.
Short address is set.
11.7.2
Activating/deactivating constant current
The constant current affects the output of current values, e.g. in the additional
display
1.
Open the operating menu with [↵].
Select “Detail setup" and confirm with [↵].
2.
Select “HART” and confirm with [↵].
3.
Select “Cons. current” and confirm with [↵].
4. Activate/deactivate constant current.
Select “on” or “off” and confirm with [↵].
Constant current is activated/deactivated.