Series EK92
EK90 smoke control dampers
Installation in flexible walls (2) Metal stud walls
EK90 smoke control dampers
either directly next to or on top of one another
in
metal stud walls
with cladding on both sides.
All dimensions in mm
Example:
Installation of two EK90 smoke control dampers
directly on top of one another.
Installation of the dampers directly underneath one another
is performed in the same way.
EK90 smoke control dampers
in
metal stud walls
with cladding on both
sides, directly adjoining rigid walls and ceilings.
Detail A:
Shear protection strips
⇒
see page 21
Detail B:
The 52 mm spacing can be
reduced to 22 mm when
using the NL or NR versions!
⇒
see pages 29 and 34.
Detail A
1000
1000
50
B + 110
50
1
+
H
100
50
1+
H
Installation opening
Installation opening
Stopper seals
W 95
UW profile
35
Shear protection
strips
Fill remaining gap
with mineral wool
Detail B
1000
1000
50
1
+
H
Installation opening
B + 110
Stopper seal
W 95
UW profile
Chipboard screws
Ø4 x 60
52
Shear protection strips
Fill remaining gap
with mineral wool