User Manual 5.32 (2018-05) 25
Subject to change
Series EK92
EK90 smoke control dampers
Lateral mounting on smoke extraction ducts (2)
All dimensions in mm
Section A-A
Detailed view
Mounting on smoke extraction ducts
with clear widths ≥ H
smoke control damper
+ 300 mm. This installation version allows
for mounting at a maximum offset of 70 mm. Flashing strips are then used for assembly.
Longitudinal
view
Installation
opening
Completed
installation
Extensions
must be produced from duct-specific materials in the cross-section 50 mm x
≤
70 mm, glued to the smoke extraction
duct and screwed on using chipboard screws with a diameter of 5 x 80 at spacings of
≤
160 mm.
Flashing strips
must be produced from duct-specific materials, glued to the smoke extraction duct and the smoke control damp
-
er, and screwed on using chipboard screws with a diameter of 4 x 80 at spacings of
≤
200 mm.
Damper blade excess length
Ü2
⇒
see page 4
Spacings of x
≥
20 mm must remain between the opened damper blade and the casing wall.
Stopper seal
Flashing strip
00
1
Extension
50
Chipboard
screws Ø5x80
07
02
2L
X
2
Ü